02 - 07
-
OUTDOOR UNIT
AO
G12-24LAL
OUTDOOR UNIT
AO
G12-24LAL
This table is created using the maximum capacity.
MODEL
:AO
G14LALL
Height difference H
1 Indoor unit is higher than outdoor unit.
2 Indoor unit is lower than outdoor unit.
Indoor unit
Indoor unit
Connection pipe
Outdoor unit
Outdoor unit
Connection pipe
HEATING
Pipe length (m)
57.510152025
Height
difference H
(m)
1
Indoor unit is
higher than
outdoor unit.
15 - - - 0.918 0.891 0.862
10 - - 0.981 0.918 0.891 0.862
7.5 - 1.000 0.981 0.918 0.891 0.862
5 1.000 1.000 0.981 0.918 0.891 0.862
0 1.000 1.000 0.981 0.918 0.891 0.862
2
Indoor unit is
lower than
outdoor unit.
-5 0.995 0.995 0.976 0.914 0.886 0.858
-7.5 - 0.993 0.974 0.912 0.884 0.856
-10 - - 0.972 0.909 0.882 0.854
-15 - - - 0.900 0.873 0.845
COOLING
Pipe length (m)
57.510152025
Height
difference H
(m)
1
Indoor unit is
higher than
outdoor unit.
15 - - - 0.953 0.950 0.947
10 - - 0.983 0.968 0.966 0.962
7.5 - 0.988 0.987 0.972 0.970 0.966
5 0.992 0.992 0.991 0.976 0.974 0.970
0 1.000 1.000 0.999 0.984 0.982 0.978
2
Indoor unit is
lower than
outdoor unit.
-5 1.000 1.000 0.999 0.984 0.982 0.978
-7.5 - 1.000 0.999 0.984 0.982 0.978
-10 - - 0.999 0.984 0.982 0.978
-15 - - - 0.984 0.982 0.978
HH