EasyManua.ls Logo

Fujitsu AUG12LVLB - Outdoor Unit - No Power

Fujitsu AUG12LVLB
67 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
-
(
02 - 09
)
-
OUTDOOR UNIT
AO
G12-24LAL
OUTDOOR UNIT
AO
G12-24LAL
This table is created using the maximum capacity.
MODEL
:AO
G24LALA
Height difference H
1 Indoor unit is higher than outdoor unit.
2 Indoor unit is lower than outdoor unit.
Indoor unit
Indoor unit
Connection pipe
Outdoor unit
Outdoor unit
Connection pipe
HEATING
Pipe length (m)
57.51015202530
Height
difference H
(m)
1
Indoor unit is
higher than
outdoor unit.
20 - - - - 0.927 0.893 0.863
10 - - 0.992 0.952 0.927 0.893 0.863
7.5 - 1.000 0.992 0.952 0.927 0.893 0.863
5 1.000 1.000 0.992 0.952 0.927 0.893 0.863
0 1.000 1.000 0.992 0.952 0.927 0.893 0.863
2
Indoor unit is
lower than
outdoor unit.
-5 0.995 0.995 0.987 0.947 0.922 0.888 0.859
-7.5 - 0.993 0.984 0.945 0.920 0.886 0.857
-10 - - 0.982 0.943 0.917 0.884 0.855
-20----0.9080.8750.846
COOLING
Pipe length (m)
57.51015202530
Height
difference H
(m)
1
Indoor unit is
higher than
outdoor unit.
20 - - - - 0.963 0.961 0.959
10 - - 0.984 0.981 0.979 0.977 0.975
7.5 - 0.988 0.988 0.985 0.983 0.981 0.979
5 0.992 0.992 0.992 0.989 0.987 0.985 0.983
0 1.000 1.000 1.000 0.997 0.995 0.993 0.991
2
Indoor unit is
lower than
outdoor unit.
-5 1.000 1.000 1.000 0.997 0.995 0.993 0.991
-7.5 - 1.000 1.000 0.997 0.995 0.993 0.991
-10 - - 1.000 0.997 0.995 0.993 0.991
-20 - - - - 0.995 0.993 0.991
HH