5-2. Outdoor unit
¢ Heatsink thermistor
Models: AOUH24LUAS1, AOUH30LUAS1, and AOUH36LUAS1
Temperature °F (°C) Resistance (kΩ) Voltage (V)
-22.0 (-30.0) 94.26 0.08
-12.0 (-25.0) 67.95 0.11
-4.0 (-20.0) 49.62 0.15
5.0 (-15.0) 36.68 0.20
14.0 (-10.0) 27.42 0.26
23.0 (-5.0) 20.73 0.34
32.0 (0.0) 15.83 0.43
41.0 (5.0) 12.21 0.55
50.0 (10.0) 9.50 0.68
59.0 (15.0) 7.46 0.84
68.0 (20.0) 5.90 1.01
77.0 (25.0) 4.71 1.21
86.0 (30.0) 3.78 1.42
95.0 (35.0) 3.06 1.64
104.0 (40.0) 2.50 1.88
113.0 (45.0) 2.05 2.11
122.0 (50.0) 1.69 2.35
131.0 (55.0) 1.40 2.58
140.0 (60.0) 1.17 2.81
149.0 (65.0) 0.98 3.02
158.0 (70.0) 0.83 3.22
167.0 (75.0) 0.70 3.41
176.0 (80.0) 0.60 3.58
185.0 (85.0) 0.51 3.73
194.0 (90.0) 0.44 3.87
203.0 (95.0) 0.38 3.99
212.0 (100.0) 0.33 4.10
5-2. Outdoor unit - (03-64) - 5. Thermistor resistance values