3-3. Setting of external input and output
• Indoor unit
Input
Connection point Function setting number 46 Function
Terminal
00 Operation/Stop mode 1
01 (Setting prohibited)
02 Forced stop mode
03 Operation/Stop mode 2
Output
Connection point Function setting number 60 Function
CN47
00 Operation/Stop
01—04 Cooling thermostat On
05 Heating thermostat On
06 Operation/Stop
07—08 Cooling thermostat On
09 Error status
10 Indoor unit fan operation status
11 External heater output
3-3. Setting of external input and output - (05-18) - 3. External input and output (for indoor unit)