3-1. External input
“Operation/Stop” mode or "Forced stop" mode can be selected with function setting of indoor unit.
A twisted pair cable (22 A→G) should be used. Maximum length of cable is 492 ft (150 m).
Use an external input and output cable with appropriate external dimension, depending on the
number of cables to be installed.
The wire connection should be separate from the power cable line.
¢
Indoor unit
Indoor unit functions such as Operation/Stop can be done by using indoor unit terminal.
1
2

Terminal
*1: The switch can be used on the following condition: DC 12 V to 24 V, 1 mA to 15 mA.
¢
External Input and Output PCB
The indoor unit Operation/Stop can be set by using the input terminal on the PCB.
Input select
Use either one of these types of terminal according to the application. (Both types of terminal can-
not be used simultaneously.)
Dry contact
In case of internal power supply, set the slide switch of S→1 to "NON VOL" side.
1
2
C
Input 1 Input 2
Ex IN
Connected device
*1 *1
+
+
-
*1: The switches can be used on the following condition: DC 12 V to 24 V, 1 mA to 15 mA.
Apply voltage
In case of external power supply, set the slide switch of S→1 to “VOL” side.
1
2
C
Input 1 Input 2 Power supply
Ex IN
Connected device
*1 *1
*2
+-
*1: The switches can be used on the following condition: DC 12 V to 24 V, 1 mA to 15 mA.
*2: Make the power supply DC 12 V to 24 V, 10 mA or more.
3-1. External input - (05-15) - 3. External input and output (for indoor unit)