7-13. Peak cut operation (for 24/30/36 model)
The current value is limited to reduce the power consumption by external input.
Peak cut level Level 1 Level 2 Level 3 Level 4
Peak cut for rated capacity
Forced thermostat
off
50% 75% 100%
NOTES:
During defrost operation, peak cut operation becomes invalid.
Even during the peak cut operation, the operations of current overload, economy, and low noise
are effective and the outdoor unit operates by lowest current of them.
7-14. Unit status monitoring and the detected value indication
The wired remote controller can monitor the indoor and outdoor units' status and display the detect-
ed result as a relevant ID.
For details of the display method, refer to the Chapter of “Display Sensor Values” in the Installation
Manual of →ired Remote Controller (Touch Panel).
The status can be monitored and displayed on the wired remote controller by assigning an arbitrary
ID. For available ID list, refer to the table below.
NOTE: Operating time for each part cannot be reset when the part is replaced. Take notes of the
operating time before replacing to count the operating time of the replaced part.
Available Sensor ID
Sensor ID Item Unit Remarks
00: Indoor unit
00 000 Suction temp. 01: °F or °C
00 001 Room temp. 01: °F or °C
→hen the wired remote controller
thermistor is enabled, temperature of
the wired remote controller thermistor
is displayed.
00 002
→ired remote controller detected
temp.
01: °F or °C
00 006 Heat exchanger middle temp. 01: °F or °C
00 020 Fan rotation number 03: rpm
00 021 Fan 2 rotation number 03: rpm
00 051 Float switch On/Off 08: On/Off
0: Off, 1: On (→hen the water level
rises)
00 052 Drain pump On/Off 08: On/Off 0: Off, 1: On
00 080 Indoor unit total energized hours 11: h
00 081 Total filtering hours 11: h
00 082 Indoor unit fan total operation hours 11: h
00 083 Indoor unit fan 2 total operation hours 11: h
00 095
Presence or absence detected by
human sensor
00: —
0: Absence, 1: Presence
—: Human sensor error or No human
sensor
00 140 Operation or Stop (External input) 00: —
0: Off, 1: On
—: →hen the function setting 46 is
not set
NOTE: Available only for external
input port of the indoor unit
7-13. Peak cut operation (for 24/30/36 model) - (04-35) - 7. Various control
CONTROL AND
FUNCTIONS
CONTROL AND
FUNCTIONS

Table of Contents

Other manuals for Fujitsu AUUH18LUAS

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fujitsu AUUH18LUAS and is the answer not in the manual?

Fujitsu AUUH18LUAS Specifications

General IconGeneral
BrandFujitsu
ModelAUUH18LUAS
CategoryAir Conditioner
LanguageEnglish

Related product manuals