1-5. Rotation number of compressor limitation by outdoor
temperature
¢ Model: AOUH18LUAS1
The minimum rotation number of compressor is limited by outdoor temperature as below.
Cooling/Dry mode
F zone
E zone
D zone
C zone
B zone
A zone
14.0°F
(-10°C)
32.0°F
(0°C)
50.0°F
(10°C)
66.2°F
(19°C)
100.4°F
(38°C)
Unit: rps
Model name Outdoor temperature zone
Limitation of compressor
frequency
AOUH18LUAS1
A zone 33
B zone 33
C zone 33
D zone 25
E zone 10
F zone 20
Heating mode
F zone
E zone
D zone
C zone
B zone
A zone
66.2°F
(19°C)
32.0°F
(0°C)
5.0°F
(-15°C)
-13.0°F
(-25°C)
41.0°F
(5°C)
Unit: rps
Model name Outdoor temperature zone
Limitation of compressor
frequency
AOUH18LUAS1
A zone 30
B zone 30
C zone 30
D zone 13
E zone 10
F zone 10
1-5. Rotation number of compressor limitation by outdoor temperature - (04-8) - 1. Rotation number control of compressor