¢ Models: AOUH24LUAS1, AOUH30LUAS1, and AOUH36LUAS1
The minimum rotation number of compressor is limited by outdoor temperature as below.
Cooling/Dry mode
69.8°F
(21°C)
44.6°F
(7°C)
55.4°F
(13°C)
100.4°F
(38°C)
122.0°F
(50°C)
125.6°F
(52°C)
107.6°F
(42°C)
F zone
E zone
D zone
C zone
B zone
A zone
G zone
H zone
Unit: rps
Model name Outdoor temperature zone
Limitation of compressor
frequency
AOUH24LUAS1
A zone 29
B zone 29
C zone 29
D zone 24
E zone 19
F zone 21
G zone 28
H zone 32
AOUH30LUAS1
AOUH36LUAS1
A zone 30
B zone 26
C zone 20
D zone 20
E zone 15
F zone 24
G zone 27
H zone 35
1-5. Rotation number of compressor limitation by outdoor temperature - (04-9) - 1. Rotation number control of compressor
CONTROL AND
FUNCTIONS
CONTROL AND
FUNCTIONS