1-2. Heating operation
A sensor (room temperature thermistor) built in indoor unit body will usually perceive difference or
variation between setting temperature and present room temperature, and controls operation rota-
tion number of compressor.
If the room temperature is 11°F (6.0°C) lower than a set temperature, the operation rotation num-
ber of compressor will attain to maximum performance.
If the room temperature is 2°F (1.0°C) higher than a set temperature, the compressor will be
stopped.
→hen the room temperature is within the range of +2°F (1.0°C) to -11°F (6.0°C) of the setting tem-
perature, the rotation number of compressor is controlled within the range shown below.
Rotation number range of compressor
Unit: rps
Model name Minimum frequency Maximum frequency
AUUH18LUAS 8 130
AUUH24LUAS 10 130
AUUH30LUAS 15 110
AUUH36LUAS 15 120
1-2. Heating operation - (04-3) - 1. Rotation number control of compressor