¢ Models: AOUH30LUAS1 and AOUH36LUAS1
Rotation number of compressor soon after starting is controlled as below.
Normal operation
Rotation
number
(rps)
I II III IV V VI VII VIII I↓
41 46 51 57 60 72 81 91 100 110
Time (sec)
1 2 3 4 5 6 7 8 9 10
60 120 180 240 360 420 480 540 600 660
Special operation
Rotation
number
(rps)
I II III IV V VI VII VIII I↓
41 46 51 57 60 72 81 91 100 110
Time (sec)
1 2 3 4 5 6 7 8 9 10
120 185 245 305 605 665 725 785 845 1,000
NOTES:
Normal operation:
Cooling and dry mode
Below 3 hours from the compressor stop and the compressor thermistor ≥ 59 °F (15 °C)
After defrost operation
Other than when the compressor starts for the first time since the breaker turns on
Special operation:
Other than the normal operation condition
→hen the compressor starts for the first time since the breaker turns on
1-4. Rotation number of compressor at normal start-up - (04-7) - 1. Rotation number control of compressor