EasyManua.ls Logo

Fujitsu AUUH18LUAS - Page 174

Fujitsu AUUH18LUAS
230 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Available Sensor ID
Sensor ID Item Unit Remarks
00 141 Emergency stop (External input) 00: —
0: Off, 1: On
—: →hen the function setting 46 is
not set
NOTE: Available only for external
input port of the indoor unit
00 142 Forced stop (External input) 00: —
0: Off, 1: On
—: →hen the function setting 46 is
not set
NOTE: Available only for external
input port of the indoor unit
00 143 Operation or Stop 2 (External input) 00: —
0: Off, 1: On
—: →hen the function setting 46 is
not set
NOTE: Available only for external
input port of the indoor unit
00 155
Operation or Stop On/Off (External
output)
00: —
0: Off, 1: On
NOTE: The value is output even if
the function setting or
rotary switch is not set.
00 156 Error On/Off (External output) 00: —
0: Off, 1: On
NOTE: The value is output even if
the function setting or
rotary switch is not set.
00 157
Indoor unit fan interlocking On/Off
(External output)
00: —
0: Off, 1: On
NOTE: The value is output even if
the function setting or
rotary switch is not set.
00 158
Cooling thermostat On/Off (External
output)
00: —
0: Off, 1: On
NOTE: The value is output even if
the function setting or
rotary switch is not set.
00 159
Requested cooling strength On/Off
(External output)
00: —
0: Off, 1: On
NOTE: The value is output even if
the function setting or
rotary switch is not set.
00 160
External heater On/Off (External
output)
00: —
0: Off, 1: On
NOTE: The value is output even if
the function setting or
rotary switch is not set.
00 161
Heating operation status (External
output)
00: —
0: Off, 1: On
NOTE: The value is output even if
the function setting or
rotary switch is not set.
00 162
External output command by remote
controller (External output)
00: —
0: Off, 1: On
NOTE: The value is output even if
the function setting or
rotary switch is not set.
01: Outdoor unit
01 000 Outdoor temp. 01: °F or °C
01 001 Discharge temp. 01: °F or °C
01 003 Heat exchanger middle temp. 01: °F or °C
01 004 Heat exchanger outlet temp. 01: °F or °C
01 007 Compressor temp. 01: °F or °C
01 008 Heat sink temp. 01: °F or °C
01 042 Gas pipe pressure for outdoor unit 02: MPa
01 050 Fan 1 rotation number 03: rpm
01 051 Fan 2 rotation number 03: rpm
01 055 Compressor rotation number 04: rps
7-14. Unit status monitoring and the detected value indication - (04-36) - 7. Various control
CONTROL AND
FUNCTIONS
CONTROL AND
FUNCTIONS

Table of Contents

Related product manuals