Available Sensor ID
Sensor ID Item Unit Remarks
01 060
Expansion valve (Upstream during
heating)
05: pls
01 080 4-way valve output status
07: Cooling/
Heating
0: Cooling, 1: Heating
01 085 Pressure switch (High pressure) 08: On/Off 0: Off (Close), 1: On (Open)
01 088 Crankcase heater output On/Off 08: On/Off 0: Off, 1: On
01 089 Base pan heater output On/Off 08: On/Off 0: Off, 1: On
01 090 Belt heater output On/Off 08: On/Off 0: Off, 1: On
01 100 Operating current 09: A
01 110 Outdoor unit total power-on hours 11: h
01 111
Compressor total heating operation
hours
11: h
01 112
Compressor total cooling operation
hours
11: h
01 113 Compressor total operation hours 11: h
01 114
Outdoor unit fan 1 total operation
hours
11: h
01 115
Outdoor unit fan 2 total operating
hours
11: h
01 145
Outdoor low noise input (External
input)
00: — 0: Off, 1: On
01 146 Outdoor peak cut (External input) 00: —
0: Off
1: Mode 4 (100%)
2: Mode 3 (75%)
3: Mode 2 (50%)
4: Mode 1 (Forced thermostat off)
01 147 Demand response (External input) 00: —
0: Normal, 1: DRM1, 2: DRM2, 3:
DRM3
01 155 Compressor status (External output) 00: — 0: Off, 1: On
01 156 Error status (External output) 00: — 0: Off, 1: On