Release condition
Model: AOUH18LUAS1
Depending on the triggering condition, different release conditions apply.
Normal defrost operation
The defrost operation is released when either one of the conditions below is satisfied.
Outdoor unit heat exchanger temperature
(after 1 minute or later since compressor start)
55.4°F (13°C) or more (Ta ≤ 33.8°F [1°C])
50.0°F (10°C) or more (Ta > 33.8°F [1°C])
Compressor operation time 15 minutes
Integrating defrost (constant monitoring)
The defrost operation is released when either one of the conditions below is satisfied.
Outdoor unit heat exchanger temperature
(after 1 minute or later since compressor start)
55.4°F (13°C) or more
Compressor operation time 15 minutes
Models: AOUH24LUAS1, AOUH30LUAS1, and AOUH36LUAS1
The defrost operation is released when either one of the conditions below is satisfied.
Outdoor unit heat exchanger temperature
(after 1 minute or later since compressor start)
53.6°F (12°C) or more
Compressor operation time 15 minutes
- (04-27) - 6. Defrost operation control