EasyManua.ls Logo

Fujitsu AUUH18LUAS - Page 208

Fujitsu AUUH18LUAS
230 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
¢
External heater output
Function
setting
External Input and
Output PCB
External output Output signal Control
Rotary switch
60-11 Output of indoor unit CN47
Off  On Heater on
On  Off Heater off
2, B, C
External Input and
Output PCB
Ex OUT 3
Off  On Heater on
On  Off Heater off
Output signal Condition
Off  On Heater turns on as shown in diagram of heating temperature
On  Off
Heater turns off as shown in diagram of heating temperature
Other than Heating mode
Error occurred
Forced thermo off
Fan stop protection
Specifications of the signal output performance are as shown as follows:
Example: →hen set temperature (Ts) is set at 72°F (22°C);
And room temperature (Tr) increase above 53.6°F (12°C), signal output is on.
And Tr increase above 69.8°F (21°C), signal output is off.
And Tr decrease below 66.2°F (19°C), signal output is on.
And Tr decrease below 50°F (10°C), signal output is off.
Off
Off
On
Tr-Ts
Tr-Ts=-1.8 °F (-1 °C)
Tr-Ts=-18 °F (-10 °C)
Tr-Ts=-5.4 °F (-3 °C)
Tr-Ts=-22 °F (-12 °C)
The output also turns off in defrost operation.
3-5. Details of control output function - (05-26) - 3. External input and output (for indoor unit)
FIELD
WORKING
FIELD
WORKING

Table of Contents

Related product manuals