Peak cut mode
By performing following on-site work, operation that suppresses the current value can be enabled:
The air conditioner is set to the “Peak cut mode” when closing the contact input of a commercial
timer or on/off switch to a connector on the control PCB of the outdoor unit.
Circuit diagram example
Outdoor unit
control PCB
Connected unit
(Locally purchased)
Example: Switch
Signal
10m*
(33ft)
Connector
1
2
1
2
P580PA580
Contact capacity: DC 24 V or more, 10 mA
or more.
*: Make the distance from the PCB to the
connected unit within 33 ft (10 m).
Construct a circuit as shown in this figure
with using optional parts mentioned below.
Input signal: On in “Peak cut mode”
Input signal: Off in normal operation
To set the level of “Peak cut mode,” refer
to "Peak cut mode" on page 05-13 (under
“Local setting procedure”.)
On
Off
On
Off
Input signal
Peak cut mode
Optional part
Part name Model name Exterior
External Connect Kit UT↔-↓→Z↓Z3
External input wire
4-1. External input - (05-46) - 4. External input and output (for 24-36 outdoor units)
FIELD
WORKING
FIELD
WORKING