4. Connection and Settings
Setting the ETERNUS DX/AF
FUJITSU Storage ETERNUS AF, ETERNUS DX Configuration Guide (Power Synchronized Unit)
Copyright 2019 FUJITSU LIMITED P3AM-8012-14ENZ0
47
Enable
Select the controllers (CM#0 and/or CM#1) of the ETERNUS DX80 S2/DX90 S2 that are connected to the power
synchronized unit with the RS232C cable.
Select "CM#0" when the power synchronized unit is connected to the PWC port on controller 0. Select "CM#1"
when the power synchronized unit is connected to the PWC port on controller 1.
When different power synchronized units are connected to controller 0 and controller 1 in a duplicated config-
uration, select both "CM#0" and "CM#1".
Delay until Shutdown (min.)
Do not change the default setting (0 minute).
Set management unit interface
Select "Power Synchronized Unit".
Power Failure Signal
"Positive" (positive logic) is automatically set.
Low Battery Signal
"Negative" (negative logic) is automatically set.
UPS Shutdown Signal
Do not select the "Enable" checkbox.
"Positive" (positive logic) is set by default.
Auto Power
Select "Disable".
Power Resume
Select "Disable".
ETERNUS DX60 S2
This section explains the setting items on the power synchronization setting screen for the ETERNUS DX60 S2.
Figure 14 ETERNUS DX60 S2 setup (Setup Power Management screen)