C120-H007-08EN 41
4.3 Air Conditioning Conditions
Figure 4.5 is an air-line diagram depicting the relationships between the dry-bulb
temperature, relative humidity, and absolute temperature.
Figure 4.5 Psychrometric chart applicable to changing the room temperature
Table 4.2 Temperature and humidity recommendations (changing the room
temperature)
Air conditioning
setup
Near the underfloor air
outlet
Detection and regulation
point
Humidity
%
Remarks
Temperature
Humidity
%
Temperature
C F C F
Direct blow or
duct blow
Setting:
Between 21
and 26 Width
of variation:
2 C
Setting:
Between 70
and 79 Width
of variation:
4F
455%
Underfloor
ventilation
181 C 642 F655% Targeted at
24 C
Targeted at
75F
About 45% at
24C (75F)
The
temperature
and humidity
depend on
the thermal
load.
Do not
change the
flow rate
even if the
underfloor
temperature
is changed.
191 C 662 F625% Targeted
between
24 and 25C
Targeted
between
75 and 77F
About 43% at
24C (75F)
20 1 C 682 F585% Targeted
between
24 and 26 C
Targeted
between
75 and 79F
About 40% at
26C (79F)
Combined use of
direct blowing or
duct blowing
and underfloor
ventilation
181 C 642 F655% 242 C754F 40 to 50% Do not
change the
flow rate
even if the
underfloor
temperature
is changed.
191
C 662 F625% 252 C774F 40 to 48%
20 1 C 68 2 F585% 262 C794F 40 to 45%