C120-H007-08EN 79
6.4 Grounding
6.4.2 Grounding other equipment
Table 6.6 summarizes the requirements for other equipment grounding facilities.
Table 6.6 Requirements for other equipment grounding facilities
Item Requirements
Grounding electrode A dedicated grounding electrode for other equipment is recommended.
If a dedicated grounding electrode is not available, a grounding trunk
cable may be branched from a shared grounding electrode.
The grounding resistance must not exceed 100 .
Keep the grounding electrode at least 10 m (33 ft) apart from the lightning
arrester grounding electrode.
Grounding trunk
cable
Use an insulated wire at least 5.5 mm
2
(AWG10).
Use the grounding trunk cable dedicated to other equipment. Do not share
with other facilities.
Distribution panel
grounding terminal
Isolate the primary grounding terminal and branch grounding terminals
for other equipment from the distribution panel frame.