EasyManua.ls Logo

Fujitsu RCF24LBL - Pipe Requirement; Flare Connection (Pipe Connection)

Fujitsu RCF24LBL
20 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
En-6
Pipe outside
diameter [mm (in.)]
Width across ats
of Flare nut [mm]
6.35 (1/4) 17
9.52 (3/8) 22
12.70 (1/2) 26
15.88 (5/8) 29
19.05 (3/4) 36
4.3.2 Bending pipes
If pipes are shaped by hand, be careful not to collapse them.
Do not bend the pipes at an angle more than 90°.
When pipes are repeatedly bend or stretched, the material
will harden, making it dif cult to bend or stretch them any
more.
Do not bend or stretch the pipes more than three times.
CAUTION
To prevent breaking of the pipe, avoid sharp bends.
If the pipe is bent repeatedly at the same place, it will
break.
4.3.3. Pipe connection
CAUTION
Be sure to apply the pipe against the port on the indoor
unit and the outdoor unit correctly. If the centering is im-
proper, the are nut cannot be tightened smoothly. If the
are nut is forced to turn, the threads will be damaged.
Do not remove the are nut from the indoor unit pipe until
immediately before connecting the connection pipe.
Do not use mineral oil on ared part. Prevent mineral
oil from getting into the system as this would reduce the
lifetime of the units.
Detach the caps and plugs from the pipes.(1)
Center the pipe against the port on the indoor unit, and (2)
then turn the are nut by hand.
Indoor unit
Connection pipe
(Liquid)
Connection pipe
(Gas)
When the are nut is tightened properly by your hand, (3)
hold the body side coupling with a separate spanner, then
tighten with a torque wrench. (See the table below for the
are nut tightening torques.
CAUTION
Hold the torque wrench at its grip, keeping it in the right
angle with the pipe, in order to tighten the are nut cor-
rectly.
Tighten the are nuts with a torque wrench using the
speci ed tightening method. Otherwise, the are nuts
could break after a prolonged period, causing refrigerant
to leak and generate a hazardous gas if the refrigerant
comes into contact with a ame.
Width across
4.2. Pipe requirement
CAUTION
Refer to the Installation Manual of the outdoor unit for
description of the length and the diameter of connecting
pipe or for difference of its elevation.
Use pipe with water-resistant heat insulation.
CAUTION
Install heat insulation around both the gas and liquid
pipes. Failure to do so may cause water leaks.
Use heat insulation with heat resistance above 120 °C.
(Reverse cycle model only)
In addition, if the humidity level at the installation loca-
tion of the refrigerant piping is expected to exceed 70%,
install heat insulation around the refrigerant piping. If the
expected humidity level is 70-80%, use heat insulation
that is 15 mm or thicker and if the expected humidity ex-
ceeds 80%, use heat insulation that is 20 mm or thicker.
If heat insulation is used that is not as thick as speci ed,
condensation may form on the surface of the insulation.
In addition, use heat insulation with heat conductivity of
0.045W/(m·K) or less (at 20 °C).
4.3. Flare connection (pipe connection)
4.3.1. Flaring
Use special pipe cutter and are tool exclusive for R410A.
Cut the connection pipe to the necessary length with a (1)
pipe cutter.
Hold the pipe downward so that cuttings will not enter the (2)
pipe and remove any burrs.
Insert the are nut (always use the are nut attached to (3)
the indoor and outdoor units respectively) onto the pipe
and perform the are processing with a are tool. Leak-
age of refrigerant may result if other are nuts are used.
Protect the pipes by pinching them or with tape to prevent (4)
dust, dirt, or water from entering the pipes.
B
Die
A
Pipe
Check if [L] is flared uniformly
and is not cracked or scratched.
L
Pipe outside
diameter
[mm (in.)]
Dimension A [mm]
Dimension B
-
0
0.4
[mm]
Flare tool for R410A,
clutch type
6.35 (1/4)
0 to 0.5
9.1
9.52 (3/8) 13.2
12.70 (1/2) 16.6
15.88 (5/8) 19.7
19.05 (3/4) 24.0
When using conventional are tools to are R410A pipes,
the dimension A should be approximately 0.5 mm more than
indicated in the table (for aring with R410A are tools) to
achieve the speci ed aring. Use a thickness gauge to meas-
ure the dimension A.

Related product manuals