1. Indoor unit power supply defective 2 Indoor unit overconnected
3.Communication line incorrect connection 4. Noise, momentary open
Outdoor unit Main PCB
Check Point 1 : Check the indoor unit power supply
Check the indoor unit power supply
Check Point 2 : Check the indoor unit number connection
Check if each indoor units are connected in a refrigerant circuit
Is it uncoupled or cut halfway ?
Connecting terminal position is correct as the installation manual shows ?
Check Point 4 : Check noise, momentary open, voltage drop
Check if power supply temporarily stops by outages or if strong noise is generated from
surrounding environment during auto address
Check Point 3 : Check the communication line connection
Indoor Unit : No Display
Outdoor Unit : E. 28. 1
Error Code : 28
Auto Address Setting Error
When none of the connected indoor units answers during auto address
And when abnormal answer signal is input.
Trouble shooting 31
Indicate or Display:
Detective Actuators:
Detective details:
OUTDOOR UNIT Error Method:
Forecast of Cause :
Check if communication line is correctly connected
E. 28. 1
04-39