OK
OK
OK
1. Signal amplifier power supply defective 2. Signal amplifier overconnected
3. Signal amplifier auto address wrong setting 4. Noise, momentary open.
Outdoor unit Main PCB
Check Point 1 : Check signal amplifier unit power supply
Check signal amplifier unit power supply
Check Point 2 : Check the signal amplifier number connection
Check if more than 8 signal amplifiers are connected in a network
Check if signal amplifier auto address is set at the same time from multiple
outdoor units (master unit)
Check Point 4 : Check noise, momentary open, voltage drop
Check if power supply temporarily stops by outages or if strong noise is generated from
surrounding environment during signal amplifier auto address
Check Point 3 : Check the operation of signal amplifier auto address setting
Indoor Unit : No Display
Outdoor Unit : E. 28. 4
Error Code : 28
Signal Amplifier Auto Address Error
When abnormal answer signal is input during signal amplifier auto address
Trouble shooting 32
Indicate or Display:
Detective Actuators:
Detective details:
OUTDOOR UNIT Error Method:
Forecast of Cause :
E. 28. 4
04-40

Table of Contents

Other manuals for Fujitsu UTP-VX90A

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fujitsu UTP-VX90A and is the answer not in the manual?

Fujitsu UTP-VX90A Specifications

General IconGeneral
BrandFujitsu
ModelUTP-VX90A
CategoryAir Conditioner
LanguageEnglish

Related product manuals