BACnet Gateway for VRF System INSTRUCTION MANUAL r1.4.0 eng
Copyright© 2021 Fujitsu General Limited - All rights reserved
5.3.44 IU_rr_uu_OperationMode_Setting (Multistate Output Object Type)
Operation mode can be set for indoor unit.
Property Identifier Property Datatype Value
ASHRAE
Object_Identifier BACnetObjectIdentifier (Multistate Output, 10rruu) R R
Object_Name CharacterString “IU_rr_uu_OperationMode_Setting” R R
Object_Type BACnetObjectType MULTISTATE_OUTPUT (14) R R
Present_Value Unsigned 1 ~ 5
W
W
Description CharacterString
-
O -
Device_Type CharacterString - O -
Status_Flags BACnetStatusFlags {FALSE, FALSE, FALSE, FALSE} R R
Event_State BACnetEventState STATE_NORMAL (0) R R
Reliability BACnetReliability NO_FAULT_DETECTED (0) O R
Out_Of_Service BOOLEAN FALSE R R
Number_Of_States Unsigned 5 R R
State_Text
BACnetArray[N] of
Check Operation Mode settings below O R
Priority_Array BACnetPriorityArray
BACnetPriorityArray
R R
Relinquish_Default Unsigned 1 R R
Time_Delay Unsigned - O R*
Notification_Class Unsigned - O R*
Feedback_Value Unsigned - O W
Event_Enable BACnetEventTransitionBits - O R*
Acked_Transitions BACnetEventTransitionBits - O R*
Notify_Type BACnetNotifyType - O R*
Event_Time_Stamps
BACnetArray[N] of
- O R*
Event_Message_Texts
BACnetArray[3] of
- O -
Event_Message_Texts_Config
BACnetArray[3] of
- O -
Event_Detection_Enable BOOLEAN - O R*
Event_Algorithm_Inhibit_Ref
BACnetObjectPropertyRefer
ence
- O -
Event_Algorithm_Inhibit BOOLEAN - O -
Time_Delay_Normal Unsigned - O -
Reliability_Evaluation_Inhibit BOOLEAN - O -
Property_List
BACnetArray[N] of
BACnetArray[N] R R
Profile_Name CharacterString - O -
* Only available when specific object has a Notification Class configured