BACnet Gateway for VRF System INSTRUCTION MANUAL r1.4.0 eng
Copyright© 2021 Fujitsu General Limited - All rights reserved
5.3.33 IU_rr_uu_Operation_Setting (Binary Output Object Type)
Operation ON/OFF can be commanded for indoor unit.
Property Identifier Property Datatype Value
ASHRAE
UTY-
Object_Identifier BACnetObjectIdentifier (Binary Output, 10rruu) R R
Object_Name CharacterString “IU_rr_uu_Operation_Setting” R R
Object_Type BACnetObjectType BINARY_OUTPUT (4) R R
Present_Value BACnetBinaryPV INACTIVE (0) / ACTIVE (1)
W
W
Description CharacterString
- O
-
Device_Type CharacterString - O -
Status_Flags BACnetStatusFlags
{FALSE, FALSE, FALSE, FALSE}
R R
Event_State BACnetEventState STATE_NORMAL (0) R R
Reliability BACnetReliability
NO_FAULT_DETECTED (0)
O R
Out_Of_Service BOOLEAN
FALSE R
R
Polarity BACnetPolarity NORMAL (0) R R
Inactive_Text CharacterString "Off" O R
Active_Text CharacterString “On" O R
Change_Of_State_Time BACnetDatetime - O -
Change_Of_State_Count Unsigned - O -
Time_Of_State_Count_Reset BACnetDatetime - O -
Elapsed_Active_Time Unsigned - O -
Time_Of_Active_Time_Reset BACnetDatetime - O -
Minimum_Off_Time Unsigned32 - O -
Minimum_On_Time Unsigned32 - O -
Priority_Array BACnetPriorityArray BACnetPriorityArray R R
Relinquish_Default BACnetBinaryPV INACTIVE (0) R R
Time_Delay Unsigned - O R*
Notification_Class Unsigned - O R*
Feedback_Value BACnetBinaryPV - O W
Event_Enable BACnetEventTransitionBits
-
O R*
Acked_Transitions BACnetEventTransitionBits
-
O R*
Notify_Type BACnetNotifyType
-
O R*
Event_Time_Stamps
BACnetArray[N] of
- O R*
Event_Message_Texts
BACnetArray[3] of
- O -
Event_Message_Texts_Config
BACnetArray[3] of
- O -