5.3.30 IU_rr_uu_Emergency_Status (Binary Input Object Type)
Indoor unit emergency stop operation status can be monitored.
Property Identifier Property Datatype Value
ASHRAE
Object_Identifier BACnetObjectIdentifier
(Binary Input, 14rruu)
R R
Object_Name CharacterString
“IU_rr_uu_Emergency_Status”
R R
Object_Type BACnetObjectType BINARY_INPUT (3) R R
Present_Value BACnetBinaryPV INACTIVE (0) / ACTIVE (1) R R
Description CharacterString - O
-
Device_Type CharacterString
-
O -
Status_Flags BACnetStatusFlags {FALSE, FALSE/TRUE, FALSE, FALSE} R R
Event_State BACnetEventState STATE_NORMAL (0) R R
Reliability BACnetReliability
NO_FAULT_DETECTED (0),
O R
Out_Of_Service BOOLEAN FALSE R R
Polarity BACnetPolarity NORMAL (0) R R
Inactive_Text CharacterString "Normal" O R
Active_Text CharacterString “Stop” O R
Change_Of_State_Time BACnetDatetime - O -
Change_Of_State_Count Unsigned - O -
Time_Of_State_Count_Reset BACnetDatetime - O -
Elapsed_Active_Time Unsigned - O -
Time_Of_Active_Time_Reset BACnetDatetime - O -
Time_Delay Unsigned - O R*
Notification_Class Unsigned - O R*
Alarm_Value BACnetBinaryPV - O R*
Event_Enable BACnetEventTransitionBits
-
O R*
Acked_Transitions BACnetEventTransitionBits
-
O R*
Notify_Type BACnetNotifyType - O R*
Event_Time_Stamps
BACnetArray[N] of
- O R*
Event_Message_Texts
BACnetArray[3] of
- O -
Event_Message_Texts_Config
BACnetArray[3] of
- O -
Event_Detection_Enable BOOLEAN - O R*
Event_Algorithm_Inhibit_Ref
BACnetObjectPropertyRefer
ence
- O -
Event_Algorithm_Inhibit BOOLEAN - O -
Time_Delay_Normal Unsigned - O -