BACnet Gateway for VRF System INSTRUCTION MANUAL r1.4.0 eng
Copyright© 2021 Fujitsu General Limited - All rights reserved
5.3.5 Gateway_ErrorCode_Status (Multistate Input Object Type)
The error code when a Gateway error occurs can be checked.
Property Identifier Property Datatype Value
ASHRAE
Object_Identifier BACnetObjectIdentifier (Multistate Input, 0) R R
Object_Name CharacterString
“Gateway_ErrorCode_Status”
R R
Object_Type BACnetObjectType MULTISTATE_INPUT (13) R R
Present_Value Unsigned 1 ~ 3 R R
Description CharacterString
-
O
-
Device_Type CharacterString - O -
Status_Flags BACnetStatusFlags {FALSE, FALSE/TRUE, FALSE, FALSE} R R
Event_State BACnetEventState
STATE_NORMAL (0)
R R
Reliability BACnetReliability
NO_FAULT_DETECTED (0),
O R
Out_Of_Service BOOLEAN FALSE R R
Number_Of_States Unsigned 3 R R
State_Text
BACnetArray[N] of
- O -
Time_Delay Unsigned - O R*
Notification_Class Unsigned - O R*
Alarm_Values List of Unsigned - O R*
Fault_Values List of Unsigned - O R*
Event_Enable BACnetEventTransitionBits
-
O R*
Acked_Transitions BACnetEventTransitionBits
-
O R*
Notify_Type BACnetNotifyType
-
O R*
Event_Time_Stamps
BACnetArray[N] of
- O R*
Event_Message_Texts
BACnetArray[3] of
CharacterString
- O -
Event_Message_Texts_Config
BACnetArray[3] of
CharacterString
- O -
Event_Detection_Enable BOOLEAN - O R*
Event_Algorithm_Inhibit_Ref
BACnetObjectPropertyRefer
ence
- O -
Event_Algorithm_Inhibit BOOLEAN - O -
Time_Delay_Normal Unsigned - O -
Reliability_Evaluation_Inhibit BOOLEAN - O -
Property_List
BACnetArray[N] of
BACnetArray[N] R R
Profile_Name CharacterString - O -
* Only available when specific object has a Notification Class configured