BACnet Gateway for VRF System INSTRUCTION MANUAL r1.4.0 eng
Copyright© 2021 Fujitsu General Limited - All rights reserved
5.3.12 IU_rr_uu_SpaceTemp_Status (Analog Input Object Type)
Indoor unit surrounding temperature status can be monitored.
Property Identifier Property Datatype Value
ASHRAE
Object_Identifier BACnetObjectIdentifier (Analog Input, 11rruu) R R
Object_Name CharacterString “IU_rr_uu_SpaceTemp_Status” R R
Object_Type BACnetObjectType ANALOG_INPUT (0) R R
Present_Value REAL 0 ~ 63.5(°C) // 30 ~ 148(°F) R R
Description CharacterString - O
-
Device_Type CharacterString - O -
Status_Flags BACnetStatusFlags {FALSE, FALSE/TRUE, FALSE, FALSE} R R
Event_State BACnetEventState
STATE_NORMAL (0)
R R
Reliability BACnetReliability
NO_FAULT_DETECTED (0),
O R
Out_Of_Service BOOLEAN FALSE R R
Update_Interval Unsigned - O -
Units BACnetEngineeringUnits Degrees Celsius (62) // Fahrenheit (64) R R
Min_Pres_Value REAL - O -
Max_Pres_Value REAL - O -
Resolution REAL - O -
COV_Increment REAL
0
O R
Time_Delay Unsigned - O R*
Notification_Class Unsigned - O R*
High_Limit REAL - O R*
Low_Limit REAL - O R*
Deadband REAL - O R*
Limit_Enable BACnetLimitEnable - O R*
Event_Enable BACnetEventTransitionBits
-
O R*
Acked_Transitions BACnetEventTransitionBits - O R*
Notify_Type BACnetNotifyType
-
O R*
Event_Time_Stamps
BACnetArray[N] of
BACnetTimeStamp
- O R*
Event_Message_Texts
BACnetArray[3] of
CharacterString
- O -
Event_Message_Texts_Config
BACnetArray[3] of
- O -
Event_Detection_Enable BOOLEAN - O R*
Event_Algorithm_Inhibit_Ref
BACnetObjectPropertyRefer
ence
- O -
Event_Algorithm_Inhibit BOOLEAN - O -