BACnet Gateway for VRF System INSTRUCTION MANUAL r1.4.0 eng
Copyright© 2021 Fujitsu General Limited - All rights reserved
5.3.6 Batch_SetTemp_Setting (Analog Output Object Type)
Property Identifier Property Datatype Value
ASHRAE
Object_Identifier BACnetObjectIdentifier (Analog Output, 0) R R
Object_Name CharacterString “Batch_SetTemp_Setting” R R
Object_Type BACnetObjectType ANALOG_OUTPUT (1) R R
Present_Value REAL 10 ~ 30(°C) // 48 ~ 88(°F) W W
Description CharacterString - O
-
Device_Type CharacterString - O -
Status_Flags BACnetStatusFlags
{FALSE, FALSE, FALSE, FALSE}
R R
Event_State BACnetEventState STATE_NORMAL (0) R R
Reliability BACnetReliability
NO_FAULT_DETECTED
O R
Out_Of_Service BOOLEAN FALSE R R
Update_Interval Unsigned - O -
Units BACnetEngineeringUnits Degrees Celsius (62) // Fahrenheit (64) R R
Min_Pres_Value REAL - O -
Max_Pres_Value REAL - O -
Resolution REAL - O -
COV_Increment REAL
1
O R
Priority_Array BACnetPriorityArray
BACnetPriorityArray
R R
Relinquish_Default Unsigned
26
R R
Time_Delay Unsigned - O R*
Notification_Class Unsigned - O R*
High_Limit REAL - O R*
Low_Limit REAL - O R*
Deadband REAL - O R*
Limit_Enable BACnetLimitEnable - O R*
Event_Enable BACnetEventTransitionBits
-
O R*
Acked_Transitions BACnetEventTransitionBits - O R*
Notify_Type BACnetNotifyType
-
O R*
Event_Time_Stamps
BACnetArray[N] of
BACnetTimeStamp
- O R*
Event_Message_Texts
BACnetArray[3] of
- O -
Event_Message_Texts_Config
BACnetArray[3] of
- O -
Event_Detection_Enable BOOLEAN - O R*