screen for a lead lag boiler plant or through the central heat setpoint screen
for a standalone boiler. The low water temperature and the minimum and
maximum outdoor temperatures can be congured through the outdoor reset
conguration screen displayed in Figure 65.
To enable warm weather shutdown for a lead lag boiler plant start from the
boiler status screen and select congure. Scroll to and select lead lag master
conguration. Select the box labeled advanced in the bottom right hand corner.
Using the left and right arrow keys scroll to the screen labeled warm weather
shutdown. The row labeled enable needs to be set to shutdown after demand
ends.
For a standalone boiler application warm weather shutdown must be congured
through a dierent screen. This screen can be found by selecting congure
from the boiler status screen. Scroll to and select warm weather shutdown
conguration and follow similar steps as above.
FIGURE 66 OUTDOOR RESET CURVES
FIGURE 67 WARM WEATHER SHUTDOWN CONFIGURATION