EasyManua.ls Logo

GE 489

GE 489
306 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
4-62 489 Generator Management Relay
GE Power Management
4.10 S9 THERMAL MODEL 4 SETPOINT PROGRAMMING
4
4.10.4 MACHINE COOLING
The 489 thermal capacity used value is reduced exponentially when the motor current is below the
OVERLOAD PICKUP
set-
point. This reduction simulates machine cooling. The cooling time constants should be entered for both stopped and run-
ning cases (the generator is assumed to be running if current is measured or the generator is offline). A machine with a
stopped rotor normally cools significantly slower than one with a turning rotor. Machine cooling is calculated using the fol-
lowing formulae:
where: TC
used
= thermal capacity used
TC
used_start
= TC
used
value caused by overload condition
TC
used_end
= TC
used
value dictated by the hot/cold curve ratio when the machine is running
(= 0 when the machine is stopped)
t
= time in minutes
τ = Cool Time Constant (running or stopped)
I
eq
= equivalent heating current
overload_pickup = overload pickup setpoint as a multiple of FLA
hot / cold = hot/cold curve ratio
Figure 4–17: THERMAL MODEL COOLING
TC
used
TC
used_start
TC
used_end
()
e
t
τ
()TC
used_end
+=
TC
used_end
I
eq
overload_pickup
-------------------------------------------


1
hot
cold
-----------


100%×=
0
25
50
75
100
0 30 60 90 120 150 180
Time in Minutes
Thermal Capacity Used
Cool Time Constant= 15 min
TCused_start= 85%
Hot/Cold Ratio= 80%
Ieq/Overload Pickup= 80%
0
25
50
75
100
0 30 60 90 120 150 180
Time in Minutes
Thermal Capacity Used
Cool Time Constant= 15 min
TCused_start= 85%
Hot/Cold Ratio= 80%
Ieq/Overload Pickup= 100%
0
25
50
75
100
0 30 60 90 120 150 180
Time in Minutes
Thermal Capacity Used
Cool Time Constant= 30 min
TCused_start= 85%
Hot/Cold Ratio= 80%
Motor Stopped after running Rated Load
TCused_end= 0%
0
25
50
75
100
0 30 60 90 120 150 180
Time in Minutes
Thermal Capacity Used
Cool Time Constant= 30 min
TCused_start= 100%
Hot/Cold Ratio= 80%
Motor Stopped after Overload Trip
TCused_end= 0%
Thermal Model Cooling, 80% Load
Thermal Model Cooling, Motor Stopped
Thermal Model Cooling, 100% Load
Thermal Model Cooling, Motor Tripped

Table of Contents

Other manuals for GE 489

Related product manuals