6-22 489 Generator Management Relay
GE Power Management
6.3 MEMORY MAP 6 COMMUNICATIONS
6
13A2 TACHOMETER ALARM 0 to 2 1 F115 0
13A3 ASSIGN ALARM RELAYS (2-5) 1 to 4 1 F50 16
13A4 TACHOMETER ALARM SPEED 101 to 175 1 %Rated F1 110
13A5 TACHOMETER ALARM DELAY 1 to 250 1 s F1 1
13A6 TACHOMETER ALARM EVENTS 0 to 1 1 F105 0
13A7 TACHOMETER TRIP 0 to 2 1 F115 0
13A8 ASSIGN TRIP RELAYS (1-4) 0 to 3 1 F50 1
13A9 TACHOMETER TRIP SPEED 101 to 175 1 %Rated F1 110
13AA TACHOMETER TRIP DELAY 1 to 250 1 s F1 1
DIGITAL INPUTS / WAVEFORM CAPTURE
13C0 ASSIGN DIGITAL INPUT 0 to 7 1 F210 0
DIGITAL INPUTS / GND. SWITCH STATUS
13D0 ASSIGN DIGITAL INPUT 0 to 7 1 F210 0
13D1 GROUND SWITCH CONTACT 0 to 1 1 F109 0
OUTPUT RELAYS / RELAY RESET MODE
1400 R1 TRIP 0 to 1 1 F117 0
1401 R2 AUXILIARY 0 to 1 1 F117 0
1402 R3 AUXILIARY 0 to 1 1 F117 0
1403 R4 AUXILIARY 0 to 1 1 F117 0
1404 R5 ALARM 0 to 1 1 F117 0
1405 R6 SERVICE 0 to 1 1 F117 0
CURRENT ELEMENTS / OVERCURRENT ALARM
1500 OVERCURRENT ALARM 0 to 2 1 F115 0
1501 ASSIGN ALARM RELAYS (2-5) 1 to 4 1 F50 16
1502 OVERCURRENT ALARM LEVEL 10 to 150 1
×
FLA F3 101
1503 OVERCURRENT ALARM DELAY 1 to 2500 1 s F2 1
1504 OVERCURRENT ALARM EVENTS 0 to 1 1 F105 0
CURRENT ELEMENTS / OFFLINE O/C
1520 OFFLINE OVERCURRENT TRIP 0 to 2 1 F115 0
1521 ASSIGN TRIP RELAYS (1-4) 0 to 3 1 F50 1
1522 OFFLINE OVERCURRENT PICKUP 5 to 100 1
×
CT F3 5
1523 OFFLINE OVERCURRENT TRIP DELAY 3 to 99 1 Cycles F1 5
CURRENT ELEMENTS / INADVERTENT ENERG.
1540 INADVERTENT ENERGIZE TRIP 0 to 2 1 F115 0
1541 ASSIGN TRIP RELAYS (1-4) 0 to 3 1 F50 1
1542 ARMING SIGNAL 0 to 1 1 F202 0
1543 INADVERTENT ENERGIZE O/C PICKUP 5 to 300 1
×
CT F3 5
1544 INADVERTENT ENERGIZE PICKUP 50 to 99 1
×
Rated V F3 50
CURRENT ELEMENTS / PHASE OVERCURRENT
1600 PHASE OVERCURRENT TRIP 0 to 2 1 F115 0
1601 ASSIGN TRIP RELAYS (1-4) 0 to 3 1 F50 1
1602 ENABLE VOLTAGE RESTRAINT 0 to 1 1 F103 0
1603 PHASE OVERCURRENT PICKUP 15 to 2000 1
×
CT F3 1000
1604 CURVE SHAPE 0 to 13 1 F128 0
1605 FLEXCURVE TRIP TIME AT 1.03
×
PU 0 to 65535 1 ms F1 65535
1606 FLEXCURVE TRIP TIME AT 1.05
×
PU 0 to 65535 1 ms F1 65535
1607 FLEXCURVE TRIP TIME AT 1.10
×
PU 0 to 65535 1 ms F1 65535
1608 FLEXCURVE TRIP TIME AT 1.20
×
PU 0 to 65535 1 ms F1 65535
1609 FLEXCURVE TRIP TIME AT 1.30
×
PU 0 to 65535 1 ms F1 65535
160A FLEXCURVE TRIP TIME AT 1.40
×
PU 0 to 65535 1 ms F1 65535
160B FLEXCURVE TRIP TIME AT 1.50
×
PU 0 to 65535 1 ms F1 65535
160C FLEXCURVE TRIP TIME AT 1.60
×
PU 0 to 65535 1 ms F1 65535
160D FLEXCURVE TRIP TIME AT 1.70
×
PU 0 to 65535 1 ms F1 65535
Table 6–1: 489 MEMORY MAP (Sheet 12 of 29)
ADDR NAME RANGE STEP UNITS FORMAT DEFAULT
1, 2, 3 See Table footnotes on page 6–39