6-24 489 Generator Management Relay
GE Power Management
6.3 MEMORY MAP 6 COMMUNICATIONS
6
1643 FLEXCURVE TRIP TIME AT 11.5
×
PU 0 to 65535 1 ms F1 65535
1644 FLEXCURVE TRIP TIME AT 12.0
×
PU 0 to 65535 1 ms F1 65535
1645 FLEXCURVE TRIP TIME AT 12.5
×
PU 0 to 65535 1 ms F1 65535
1646 FLEXCURVE TRIP TIME AT 13.0
×
PU 0 to 65535 1 ms F1 65535
1647 FLEXCURVE TRIP TIME AT 13.5
×
PU 0 to 65535 1 ms F1 65535
1648 FLEXCURVE TRIP TIME AT 14.0
×
PU 0 to 65535 1 ms F1 65535
1649 FLEXCURVE TRIP TIME AT 14.5
×
PU 0 to 65535 1 ms F1 65535
164A FLEXCURVE TRIP TIME AT 15.0
×
PU 0 to 65535 1 ms F1 65535
164B FLEXCURVE TRIP TIME AT 15.5
×
PU 0 to 65535 1 ms F1 65535
164C FLEXCURVE TRIP TIME AT 16.0
×
PU 0 to 65535 1 ms F1 65535
164D FLEXCURVE TRIP TIME AT 16.5
×
PU 0 to 65535 1 ms F1 65535
164E FLEXCURVE TRIP TIME AT 17.0
×
PU 0 to 65535 1 ms F1 65535
164F FLEXCURVE TRIP TIME AT 17.5
×
PU 0 to 65535 1 ms F1 65535
1650 FLEXCURVE TRIP TIME AT 18.0
×
PU 0 to 65535 1 ms F1 65535
1651 FLEXCURVE TRIP TIME AT 18.5
×
PU 0 to 65535 1 ms F1 65535
1652 FLEXCURVE TRIP TIME AT 19.0
×
PU 0 to 65535 1 ms F1 65535
1653 FLEXCURVE TRIP TIME AT 19.5
×
PU 0 to 65535 1 ms F1 65535
1654 FLEXCURVE TRIP TIME AT 20.0
×
PU 0 to 65535 1 ms F1 65535
1655 OVERCURRENT CURVE MULTIPLIER 0 to 100000 1 F14 100
1657 OVERCURRENT CURVE RESET 0 to 1 1 F201 0
1658 VOLTAGE LOWER LIMIT 10 to 60 1 % F1 10
CURRENT ELEMENTS / NEGATIVE SEQUENCE
1700 NEGATIVE SEQUENCE ALARM 0 to 2 1 F115 0
1701 ASSIGN ALARM RELAYS (2-5) 1 to 4 1 F50 16
1702 NEG. SEQUENCE ALARM PICKUP 3 to 100 1 %FLA F1 3
1703 NEGATIVE SEQUENCE ALARM DELAY 1 to 1000 1 s F2 50
1704 NEGATIVE SEQUENCE ALARM EVENTS 0 to 1 1 F105 0
1705 NEGATIVE SEQUENCE O/C TRIP 0 to 2 1 F115 0
1706 ASSIGN TRIP RELAYS (1-4) 0 to 3 1 F50 1
1707 NEG. SEQUENCE O/C TRIP PICKUP 3 to 100 1 %FLA F1 8
1708 NEG. SEQUENCE O/C CONSTANT K 1 to 100 1 F1 1
1709 NEG. SEQUENCE O/C MAX. TIME 10 to 1000 1 s F1 1000
170A NEG. SEQUENCE O/C RESET RATE 0 to 9999 1 s F2 2270
CURRENT ELEMENTS / GROUND O/C
1720 GROUND OVERCURRENT ALARM 0 to 2 1 F115 0
1721 ASSIGN ALARM RELAYS (2-5) 1 to 4 1 F50 16
1722 GROUND O/C ALARM PICKUP 5 to 2000 1
×
CT F3 20
1723 GROUND O/C ALARM DELAY 0 to 100 1 Cycles F1 0
1724 GROUND OVERCURRENT ALARM EVENTS 0 to 1 1 F105 0
1725 GROUND OVERCURRENT TRIP 0 to 2 1 F115 0
1726 ASSIGN TRIP RELAYS (1-4) 0 to 3 1 F50 1
1727 GROUND O/C TRIP PICKUP 5 to 2000 1
×
CT F3 20
1728 CURVE SHAPE 0 to 13 1 F128 0
1729 FLEXCURVE TRIP TIME AT 1.03
×
PU 0 to 65535 1 ms F1 65535
172A FLEXCURVE TRIP TIME AT 1.05
×
PU 0 to 65535 1 ms F1 65535
172B FLEXCURVE TRIP TIME AT 1.10
×
PU 0 to 65535 1 ms F1 65535
172C FLEXCURVE TRIP TIME AT 1.20
×
PU 0 to 65535 1 ms F1 65535
172D FLEXCURVE TRIP TIME AT 1.30
×
PU 0 to 65535 1 ms F1 65535
172E FLEXCURVE TRIP TIME AT 1.40
×
PU 0 to 65535 1 ms F1 65535
172F FLEXCURVE TRIP TIME AT 1.50
×
PU 0 to 65535 1 ms F1 65535
1730 FLEXCURVE TRIP TIME AT 1.60
×
PU 0 to 65535 1 ms F1 65535
1731 FLEXCURVE TRIP TIME AT 1.70
×
PU 0 to 65535 1 ms F1 65535
1732 FLEXCURVE TRIP TIME AT 1.80
×
PU 0 to 65535 1 ms F1 65535
Table 6–1: 489 MEMORY MAP (Sheet 14 of 29)
ADDR NAME RANGE STEP UNITS FORMAT DEFAULT
1, 2, 3 See Table footnotes on page 6–39