GE Power Management
489 Generator Management Relay A-3
APPENDIX A A.1 COMMISSIONING
A
GENERAL INPUT E GENERAL INPUT G
Assi
n Di
ital Input None Assi
n Di
ital Input None
Asserted Di
ital Input State Closed Asserted Di
ital Input State Closed
Input Name Input E Input Name Input G
Block Input From Online 0 sec. Block Input From Online 0 sec.
General Input E Control Off General Input G Control Off
Pulsed Control Relay Dwell
Time
0.0 sec. Pulsed Control Relay Dwell
Time
0.0 sec.
Assi
n Control Relays ---- Assi
n Control Relays ----
General Input E Control Events Off General Input G Control Events Off
General Input E Alarm Off General Input G Alarm Off
Assi
n Alarm Relays ---- Assi
n Alarm Relays ----
General Input E Alarm Delay 5.0 sec. General Input G Alarm Delay 5.0 sec.
General Input E Alarm Events Off General Input G Alarm Events Off
General Input E Trip Off General Input G Trip Off
Assi
n Trip Relays ---- Assi
n Trip Relays ----
General Input E Trip Delay 5.0 sec. General Input G Trip Delay 5.0 sec.
GENERAL INPUT F REMOTE RESET
Assi
n Di
ital Input None Assi
n Di
ital Input None
Asserted Di
ital Input State Closed TEST INPUT
Input Name Input F Assi
n Di
ital Input None
Block Input From Online 0 sec.
THERMAL RESET
General Input F Control Off Assi
n Di
ital Input None
Pulsed Control Relay Dwell
Time
0.0 sec.
DUAL SETPOINTS
Assi
n Control Relays ---- Assi
n Di
ital Input None
General Input F Control Events Off Activate Setpoint Group Group 1
General Input F Alarm Off Edit Setpoint Group Group 1
Assi
n Alarm Relays ---- SEQUENTIAL TRIP
General Input F Alarm Delay 5.0 sec. Assi
n Di
ital Input None
General Input F Alarm Events Off Sequential Trip Type Low Fwd Pwr
General Input F Trip Off Assi
n Trip Relays ----
Assi
n Trip Relays ---- Sequential Trip Level 0.05 × Rated
General Input F Trip Delay 5.0 sec. Sequential Trip Delay 1.0 sec.
Table A–3: SETPOINTS PAGE 3 – DIGITAL INPUTS (Sheet 2 of 3)
DESCRIPTION DEFAULT USER VALUE DESCRIPTION DEFAULT USER VALUE