4 SETPOINT PROGRAMMING 4.7 S6 VOLTAGE ELEMENTS
4
4.7.3 VOLTS/HERTZ
The Volts/Hertz elements may be used generator and unit transformer protection. They are active as soon as the magni-
tude and frequency of
V
ab
is measurable. The alarm element is definite time; the trip element can be definite time or a
curve. Once the V/Hz measurement
V
ab
exceeds the pickup level for the specified time, a trip or alarm will occur. The reset
rate is a linear reset time from the threshold of trip and should be set to match cooling characteristics of the protected
equipment. The measurement of V/Hz will be accurate through a frequency range of 5 to 90 Hz. Settings less than 1.00
only apply for special generators such as short circuit testing machines.
VOLTS/HERTZ
[ENTER] for more
VOLTS/HERTZ
ALARM: Off
Range: Off, Latched, Unlatched
ASSIGN ALARM
RELAYS (2-5): ---5
Range: Any combination of Relays 2 to 5
VOLTS/HERTZ ALARM
PICKUP: 1.00 x Nominal
Range: 0.50 to 1.99
×
Nominal in steps of 0.01
VOLTS/HERTZ ALARM
DELAY: 3.0 s
Range: 0.1 to 150.0 s in steps of 0.1
VOLTS/HERTZ ALARM
EVENTS: Off
Range: On, Off
VOLTS/HERTZ
TRIP: Off
Range: Off, Latched, Unlatched
ASSIGN TRIP
RELAYS (1-4): 1---
Range: Any combination of Relays 1 to 4
VOLTS/HERTZ TRIP
PICKUP: 1.00 x Nominal
Range: 0.50 to 1.99
×
Rated in steps of 0.01
VOLTS/HERTZ TRIP
DELAY: 1.0 s
Range: 0.1 to 150.0 s in steps of 0.1
VOLTS/HERTZ CURVE
RESET RATE: 1.4 s
Range: 0.0 to 999.9 s in steps of 0.1
VOLTS/HERTZ TRIP
ELEMENT: Curve #1
Range: Curve #1, Curve #2, Curve #3, Definite Time
The formula for volts/hertz curve 1 is:
where:
T
= trip time in seconds
D
=
VOLTS/HERTZ TRIP DELAY
setpoint
V
= RMS measurement of Vab
F
= frequency of Vab
V
NOM
= generator voltage setpoint
F
S
= generator frequency setpoint
Pickup =
VOLTS/HERTZ TRIP PICKUP
setpoint
The V/Hz Curve 1 trip curves are shown on the right
for delay settings of 0.1, 0.3, 1, 3, and 10 seconds.
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
T
D
VF
⁄
V
nom
F
s
⁄()
Pickup
×
-----------------------------------------------------
2
1–
----------------------------------------------------------------------= , when
V
F
----
Pickup
>
0.01
0.1
1
10
100
1000
1.00 1.20 1.40 1.60 1.80 2.00
Multiples of Volts/Hertz Pickup
10
3
1
0.3
TIME DELAY SETTING
Time to Trip (seconds)
0.1