46
NEMA 1 indoor — floor plan and cable space details
Note: Refer to installation drawing and AKD-10 switchgear installation manual (DEH-194) for additional information
Refer to Table 32.1 and 32.2 for equipment depth options.
A Direction Rear P
Equipment of J Extension Transformer Flange CL
Depth Cables Depth to Rear of Switchgear
60” Non-fused
Below
19.00
or (482mm) 26.50
67” with Fused
Above
24.00
None
(673mm)
WPF-08 / 16 (609mm)
67” Non-fused
Below
26.00
or (660mm) 7.00 33.50
74” with Fused
Abov
e
31.00 (177mm) (851mm)
WPF-08 / 16 (787mm)
74” Non-fused
Below
33.00
or (838mm) 14.00 40.50
81” with Fused
Abov
e
38.00 (355mm) (1029mm)
WPF-08 / 16 (965mm)
Below
19.00
74” with (482mm) 26.50
WPS / WPX-50
Above
24.00
None
(673mm)
(609mm)
Below
26.00
81” with
(660mm) 7.00 33.50
WPS / WP
X-50
Above
31.00
(177mm) (851mm)
(787mm)
67” w/ 5000 Amp Bus
Below
19.00
w/o WPS / WPX-50
(482mm)
29.50
w/o WPF-08 / 16
Above
24.00
None
(749mm)
(609mm)
Below
26.00
74” w/ 5000 Amp Bus
(660mm)
7.00 36.50
w/o WPS / WPX-50
Above
31.00
(177mm) (927mm)
w/o WPF-08 / 16
(787mm)
NOTES:
À
CABLES ABOVE – AVAILABLE SPACE FOR CABLES REDUCED BY 5.00” (127mm)
IF
BUS C
OMPARTMENT BARRIERS ARE PROVIDED
CABLES BELOW – AVAILABLE SPACE FOR CABLES REDUCED BY 4.00 (101mm)
IF 800-2000A
BREAKER IS LOCATED IN BOTTOM COMPARTMENT.
CABLES
ABO
VE OR BEL
OW – A
V
AILABLE SPACE FOR CABLES REDUCED BY
3.00” (76mm) FOR ANY SECTION C
ONT
AINING A 5000A BREAKER
AND B
ARE 5000A BUS (IF BUS COMPARTMENT BARRIERS ARE
SUPPLIED, SEE NOTE ABOVE)
Á
SPACE REQUIRED FOR UPPER NEUTRAL WITH LEADS ABOVE OR LOWER
NEUTRAL WITH LEADS BELOW