GE Multilin B30 Bus Differential System B-39
APPENDIX B B.4 MEMORY MAPPING
B
5B09 Neutral Time Overcurrent 1 Target 0 to 2 --- 1 F109 0 (Self-reset)
5B0A Neutral Time Overcurrent 1 Events 0 to 1 --- 1 F102 0 (Disabled)
5B0B Reserved (6 items) 0 to 1 --- 1 F001 0
5B11 ...Repeated for Neutral Time Overcurrent 2
5B22 ...Repeated for Neutral Time Overcurrent 3
5B33 ...Repeated for Neutral Time Overcurrent 4
5B44 ...Repeated for Neutral Time Overcurrent 5
5B55 ...Repeated for Neutral Time Overcurrent 6
Neutral Instantaneous Overcurrent (Read/Write Grouped Setting) (6 modules)
5C00 Neutral Instantaneous Overcurrent 1 Function 0 to 1 --- 1 F102 0 (Disabled)
5C01 Neutral Instantaneous Overcurrent 1 Signal
Source
0 to 5 --- 1 F167 0 (SRC 1)
5C02 Neutral Instantaneous Overcurrent 1 Pickup 0 to 30 pu 0.001 F001 1000
5C03 Neutral Instantaneous Overcurrent 1 Delay 0 to 600 s 0.01 F001 0
5C04 Neutral Instantaneous Overcurrent 1 Reset Delay 0 to 600 s 0.01 F001 0
5C05 Neutral Instantaneous Overcurrent 1 Block 0 to 4294967295 --- 1 F300 0
5C07 Neutral Instantaneous Overcurrent 1 Target 0 to 2 --- 1 F109 0 (Self-reset)
5C08 Neutral Instantaneous Overcurrent 1 Events 0 to 1 --- 1 F102 0 (Disabled)
5C09 Reserved (8 items) 0 to 1 --- 1 F001 0
5C11 ...Repeated for Neutral Instantaneous Overcurrent
2
5C22 ...Repeated for Neutral Instantaneous Overcurrent
3
5C33 ...Repeated for Neutral Instantaneous Overcurrent
4
5C44 ...Repeated for Neutral Instantaneous Overcurrent
5
5C55 ...Repeated for Neutral Instantaneous Overcurrent
6
Ground Time Overcurrent (Read/Write Grouped Setting) (6 modules)
5D00 Ground Time Overcurrent 1 Function 0 to 1 --- 1 F102 0 (Disabled)
5D01 Ground Time Overcurrent 1 Signal Source 0 to 5 --- 1 F167 0 (SRC 1)
5D02 Ground Time Overcurrent 1 Input 0 to 1 --- 1 F122 0 (Phasor)
5D03 Ground Time Overcurrent 1 Pickup 0 to 30 pu 0.001 F001 1000
5D04 Ground Time Overcurrent 1 Curve 0 to 16 --- 1 F103 0 (IEEE Mod
Inv)
5D05 Ground Time Overcurrent 1 Multiplier 0 to 600 --- 0.01 F001 100
5D06 Ground Time Overcurrent 1 Reset 0 to 1 --- 1 F104 0
(Instantaneou
s)
5D07 Ground Time Overcurrent 1 Block 0 to 4294967295 --- 1 F300 0
5D09 Ground Time Overcurrent 1 Target 0 to 2 --- 1 F109 0 (Self-reset)
5D0A Ground Time Overcurrent 1 Events 0 to 1 --- 1 F102 0 (Disabled)
5D0B Reserved (6 items) 0 to 1 --- 1 F001 0
5D11 ...Repeated for Ground Time Overcurrent 2
5D22 ...Repeated for Ground Time Overcurrent 3
5D33 ...Repeated for Ground Time Overcurrent 4
5D44 ...Repeated for Ground Time Overcurrent 5
5D55 ...Repeated for Ground Time Overcurrent 6
Ground Instantaneous Overcurrent (Read/Write Grouped Setting) (6 modules)
5DA0 Ground Instantaneous Overcurrent 1 Function 0 to 1 --- 1 F102 0 (Disabled)
5DA1 Ground Instantaneous Overcurrent 1 Signal
Source
0 to 5 --- 1 F167 0 (SRC 1)
Table B–10: MODBUS MEMORY MAP (Sheet 31 of 64)