B-40 B30 Bus Differential System GE Multilin
B.4 MEMORY MAPPING APPENDIX B
B
5DA2 Ground Instantaneous Overcurrent 1 Pickup 0 to 30 pu 0.001 F001 1000
5DA3 Ground Instantaneous Overcurrent 1 Delay 0 to 600 s 0.01 F001 0
5DA4 Ground Instantaneous Overcurrent 1 Reset Delay 0 to 600 s 0.01 F001 0
5DA5 Ground Instantaneous Overcurrent 1 Block 0 to 4294967295 --- 1 F300 0
5DA7 Ground Instantaneous Overcurrent 1 Target 0 to 2 --- 1 F109 0 (Self-reset)
5DA8 Ground Instantaneous Overcurrent 1 Events 0 to 1 --- 1 F102 0 (Disabled)
5DA9 Reserved (8 items) 0 to 1 --- 1 F001 0
5DB1 ...Repeated for Ground Instantaneous Overcurrent
2
5DC2 ...Repeated for Ground Instantaneous Overcurrent
3
5DD3 ...Repeated for Ground Instantaneous Overcurrent
4
5DE4 ...Repeated for Ground Instantaneous Overcurrent
5
5DF5 ...Repeated for Ground Instantaneous Overcurrent
6
Setting Groups (Read/Write Setting)
5F70 Setting Group for Modbus Comms (0 means group
1)
0 to 5 --- 1 F001 0
5F71 Setting Groups Block 0 to 4294967295 --- 1 F300 0
5F73 FlexLogic Operands to Activate Groups 2 through
6 (5 items)
0 to 4294967295 --- 1 F300 0
5F7D Setting Group Function 0 to 1 --- 1 F102 0 (Disabled)
5F7E Setting Group Events 0 to 1 --- 1 F102 0 (Disabled)
Setting Groups (Read Only)
5F7F Current Setting Group 0 to 5 --- 1 F001 0
Setting Group Names (Read/Write Setting)
5F8C Setting Group 1 Name --- --- --- F203 (none)
5F94 Setting Group 2 Name --- --- --- F203 (none)
5F9C Setting Group 3 Name --- --- --- F203 (none)
5FA4 Setting Group 4 Name --- --- --- F203 (none)
5FAC Setting Group 5 Name --- --- --- F203 (none)
5FB4 Setting Group 6 Name --- --- --- F203 (none)
Bus Configuration (Read/Write Setting) (2 modules)
64B0 Bus Zone xA Source (6 items) 0 to 5 --- 1 F167 0 (SRC 1)
64B6 Bus Zone xA Status (6 items) 0 to 4294967295 --- 1 F300 0
64C2 ...Repeated for Bus Zone 2
Bus Differential (Read/Write Grouped Setting) (4 modules)
64E0 Bus Zone 1 Function 0 to 1 --- 1 F102 0 (Disabled)
64E1 Bus Zone 1 Pickup 0.05 to 6 pu 0.001 F001 100
64E2 Bus Zone 1 Low Slope 15 to 100 % 1 F001 25
64E3 Bus Zone 1 Low Breakpoint 1 to 30 pu 0.01 F001 200
64E4 Bus Zone 1 High Slope 50 to 100 % 1 F001 60
64E5 Bus Zone 1 High Breakpoint 1 to 30 pu 0.01 F001 800
64E6 Bus Zone 1 High Set 0.1 to 99.99 pu 0.01 F001 1500
64E7 Bus Zone 1 Seal In 0 to 65.535 s 0.001 F001 400
64E8 Bus Zone 1 Block 0 to 4294967295 --- 1 F300 0
64EA Bus Zone 1 Events 0 to 1 --- 1 F102 0 (Disabled)
64EB Bus Zone 1 Target 0 to 2 --- 1 F109 0 (Self-reset)
64F8 ...Repeated for Bus Zone 2
6510 ...Repeated for Bus Zone 3
Table B–10: MODBUS MEMORY MAP (Sheet 32 of 64)
ADDR REGISTER NAME RANGE UNITS STEP FORMAT DEFAULT