GE Multilin B30 Bus Differential System B-41
APPENDIX B B.4 MEMORY MAPPING
B
6528 ...Repeated for Bus Zone 4
CT Trouble (Read/Write Setting) (2 modules)
65A0 CT Trouble 1 Function 0 to 1 --- 1 F102 0 (Disabled)
65A1 CT Trouble 1 Pickup 0.02 to 2 pu 0.001 F001 100
65A2 CT Trouble 1 Delay 1 to 60 s 0.1 F001 100
65A3 CT Trouble 1 Target 0 to 2 --- 1 F109 0 (Self-reset)
65A4 CT Trouble 1 Events 0 to 1 --- 1 F102 0 (Disabled)
65A5 ...Repeated for CT Trouble 2
Phase Undervoltage (Read/Write Grouped Setting) (3 modules)
7000 Phase Undervoltage 1 Function 0 to 1 --- 1 F102 0 (Disabled)
7001 Phase Undervoltage 1 Signal Source 0 to 5 --- 1 F167 0 (SRC 1)
7002 Phase Undervoltage 1 Pickup 0 to 3 pu 0.001 F001 1000
7003 Phase Undervoltage 1 Curve 0 to 1 --- 1 F111 0 (Definite
Time)
7004 Phase Undervoltage 1 Delay 0 to 600 s 0.01 F001 100
7005 Phase Undervoltage 1 Minimum Voltage 0 to 3 pu 0.001 F001 100
7006 Phase Undervoltage 1 Block 0 to 4294967295 --- 1 F300 0
7008 Phase Undervoltage 1 Target 0 to 2 --- 1 F109 0 (Self-reset)
7009 Phase Undervoltage 1 Events 0 to 1 --- 1 F102 0 (Disabled)
700A Phase Undervoltage 1 Measurement Mode 0 to 1 --- 1 F186 0 (Phase to
Ground)
700B Reserved (6 items) 0 to 1 --- 1 F001 0
7011 ...Repeated for Phase Undervoltage 2
7022 ...Repeated for Phase Undervoltage 3
Disconnect (Breaker) Switch (Read/Write Setting) (24 modules)
74A0 Disconnect Switch 1 Function 0 to 1 --- 1 F102 0 (Disabled)
74A1 Disconnect Switch 1 Name --- --- --- F206 “SW 1"
74A4 Disconnect Switch 1 Mode 0 to 1 --- 1 F157 0 (3-Pole)
74A5 Disconnect Switch 1 Open 0 to 4294967295 --- 1 F300 0
74A7 Disconnect Switch 1 Block Open 0 to 4294967295 --- 1 F300 0
74A9 Disconnect Switch 1 Close 0 to 4294967295 --- 1 F300 0
74AB Disconnect Switch 1 Block Close 0 to 4294967295 --- 1 F300 0
74AD Disconnect Switch 1 Phase A / Three-pole Closed 0 to 4294967295 --- 1 F300 0
74AF Disconnect Switch 1 Phase A / Three-pole Opened 0 to 4294967295 --- 1 F300 0
74B1 Disconnect Switch 1 Phase B Closed 0 to 4294967295 --- 1 F300 0
74B3 Disconnect Switch 1 Phase B Opened 0 to 4294967295 --- 1 F300 0
74B5 Disconnect Switch 1 Phase C Closed 0 to 4294967295 --- 1 F300 0
74B7 Disconnect Switch 1 Phase C Opened 0 to 4294967295 --- 1 F300 0
74B9 Disconnect Switch 1 Operate Time 0 to 65.535 s 0.001 F001 70
74BA Disconnect Switch 1 Alarm Delay 0 to 65.535 s 0.001 F003 0
74BC Disconnect Switch 1 Events 0 to 1 --- 1 F102 0 (Disabled)
74BD Reserved (2 items) --- --- --- F001 0
74BF ...Repeated for Disconnect Switch 2
74DE ...Repeated for Disconnect Switch 3
74FD ...Repeated for Disconnect Switch 4
751C ...Repeated for Disconnect Switch 5
753B ...Repeated for Disconnect Switch 6
755A ...Repeated for Disconnect Switch 7
7579 ...Repeated for Disconnect Switch 8
7598 ...Repeated for Disconnect Switch 9