B-44 B30 Bus Differential System GE Multilin
B.4 MEMORY MAPPING APPENDIX B
B
81C1 Reserved Register T2 -55 to 125 C 1 F002 125
81C2 Reserved Register T3 -2147483647 to
2147483647
--- 1 F004 0
81C4 Reserved Register T4 0 to 4294967295 --- 1 F003 0
81C6 Reserved Register T5 0 to 4294967295 --- 1 F003 0
81C8 Reserved Register T6 0 to 4294967295 --- 1 F003 0
81CA Reserved Register T7 0 to 4294967295 --- 1 F003 0
81CC Reserved Register T8 0 to 4294967295 --- 1 F003 0
EGD Fast Production Status (Read Only Non-Volatile and Read Only)
83E0 EGD Fast Producer Exchange 1 Signature 0 to 65535 --- 1 F001 0
83E1 EGD Fast Producer Exchange 1 Configuration
Time
0 to 4294967295 --- --- F003 0
83E3 EGD Fast Producer Exchange 1 Size 0 to 65535 --- 1 F001 0
EGD Slow Production Status (Read Only Non-Volatile and Read Only) (2 modules)
83F0 EGD Slow Producer Exchange 1 Signature 0 to 65535 --- 1 F001 0
83F1 EGD Slow Producer Exchange 1 Configuration
Time
0 to 4294967295 --- --- F003 0
83F3 EGD Slow Producer Exchange 1 Size 0 to 65535 --- 1 F001 0
83F4 ...Repeated for EGD Slow Producer Exchange 2
EGD Fast Production (Read/Write Setting)
8400 EGD Fast Producer Exchange 1 Function 0 to 1 --- 1 F102 0 (Disabled)
8401 EGD Fast Producer Exchange 1 Destination 0 to 4294967295 --- 1 F003 0
8403 EGD Fast Producer Exchange 1 Data Rate 50 to 1000 ms 50 F001 1000
8404 EGD Fast Producer Exchange 1 Data Item 1 (20
items)
0 to 65535 --- 1 F001 0
8418 Reserved (80 items) --- --- --- F001 0
EGD Slow Production (Read/Write Setting) (2 modules)
8468 EGD Slow Producer Exchange 1 Function 0 to 1 --- 1 F102 0 (Disabled)
8469 EGD Fast Producer Exchange 1 Destination 0 to 4294967295 --- 1 F003 0
846B EGD Slow Producer Exchange 1 Data Rate 500 to 1000 ms 50 F001 1000
846C EGD Slow Producer Exchange 1 Data Item 1 (50
items)
0 to 65535 --- 1 F001 0
849E Reserved (50 items) --- --- --- F001 0
84D0 ...Repeated for EGD Exchange 2
Breaker Failure (Read/Write Grouped Setting) (6 modules)
8600 Breaker Failure 1 Function 0 to 1 --- 1 F102 0 (Disabled)
8601 Breaker Failure 1 Mode 0 to 1 --- 1 F157 0 (3-Pole)
8602 Breaker Failure 1 Source 0 to 5 --- 1 F167 0 (SRC 1)
8603 Breaker Failure 1 Amp Supervision 0 to 1 --- 1 F126 1 (Yes)
8604 Breaker Failure 1 Use Seal-In 0 to 1 --- 1 F126 1 (Yes)
8605 Breaker Failure 1 Three Pole Initiate 0 to 4294967295 --- 1 F300 0
8607 Breaker Failure 1 Block 0 to 4294967295 --- 1 F300 0
8609 Breaker Failure 1 Phase Amp Supv Pickup 0.001 to 30 pu 0.001 F001 1050
860A Breaker Failure 1 Neutral Amp Supv Pickup 0.001 to 30 pu 0.001 F001 1050
860B Breaker Failure 1 Use Timer 1 0 to 1 --- 1 F126 1 (Yes)
860C Breaker Failure 1 Timer 1 Pickup 0 to 65.535 s 0.001 F001 0
860D Breaker Failure 1 Use Timer 2 0 to 1 --- 1 F126 1 (Yes)
860E Breaker Failure 1 Timer 2 Pickup 0 to 65.535 s 0.001 F001 0
860F Breaker Failure 1 Use Timer 3 0 to 1 --- 1 F126 1 (Yes)
8610 Breaker Failure 1 Timer 3 Pickup 0 to 65.535 s 0.001 F001 0
8611 Breaker Failure 1 Breaker Status 1 Phase A/3P 0 to 4294967295 --- 1 F300 0
Table B–10: MODBUS MEMORY MAP (Sheet 36 of 64)
ADDR REGISTER NAME RANGE UNITS STEP FORMAT DEFAULT

Table of Contents