EasyManua.ls Logo

GE DewPro MMY30 - Page 36

GE DewPro MMY30
47 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Troubleshooting 5-1
November 2005
Problems and
Recommended Solutions
Problem: The loop current is outside the range of 4-20 mA, as
shown on display or current meter. In some cases, 22 mA
can be ordered as the fault current.
Solution: The process dewpoint is out of range. If the dewpoint is
above +10°C (+50°F), the current will go to 22 mA.
Apply dry air for 20 minutes. If the dewpoint doesn't
decrease, consult the factory.
If the dewpoint is below -90°C (-130°F), the current will
go below 4 mA and then to 22 mA as fault current.
Expose the DewPro to ambient air for several minutes. If
the error remains, the cause may be a defective sensor
assembly or an electronics malfunction. Consult the
factory.
Problem: There is no current.
Solution: Check the voltage and polarity across +/- terminals with a
DC voltmeter. If the voltage is within 12-28 VDC,
consult the factory.
Problem: The response time is very slow.
Solution: Verify the flow with an air flowmeter. If the orifice is at
the outlet of a 7 to 8 bar (=100 psig) process pressure, the
air flow should indicate 20 to 30 1/h (500 cc/min., 1 cfh).
If the flow is dramatically lower, the inlet filter may be
clogged. Remove the 2 micron filter and clean it with a
solvent or replace it.
Removing the Filter Figure 5-1 below shows a breakdown of filter parts for removal.
Figure 5-1: Filter Parts

Table of Contents

Related product manuals