1.4 Storage
Store the UPS with its batteries fully charged in a dry location, storage temperature must be within -20
and +45°C.
If the unit is stored for an extended period of time, the batteries must be recharged periodically.
Connect the unit to the mains and switch it on:
- if the storage temperature is within -20 and +30°C, recharge the batteries every 3 months, for 24
hours,
- if the storage temperature is within -20 and +45°C, recharge the batteries every month, for 24 hours.
1.5 Batteries
NOTE: All maintenance and service work, including battery replacement, should be performed by
qualified service personnel.
When replacing the batteries, use only the same type and size battery.
Never short circuit batteries. When working with batteries, remove watches, rings or other metal
objects, and use only insulated tools.
Avoid charging in a sealed container.
Never dispose of batteries in a fire: they may explode.
Do not open or mutilate batteries: their contents may be extremely toxic. If exposed to electrolyte, wash
immediately with plenty of water.
Proper disposal or recycling of the batteries is required. Refer to your local codes for disposal
requirements.
OPM_LPE_11X_3K0_10K_1GB_V041 4 GE DE LP 11 UPS: User manual 4.1 (GB)