GE Masoneilan 12420 - 7.3.3. Calibration on Site with Process Fluids

GE Masoneilan 12420
80 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
® 2014 General Electric Company. All rights reserved. Masoneilan 12400 Series Transmitter/Controller Instruction Manual | 29
d. High Level [SPAN]
d1. Liquid application:
Attach to the torque arm a set of weights equivalent to the apparent weight of the displacer fully immersed in the
calibration fluid with Specific Gravity of Calibration [SG CALIB], i.e.:
d2. Interface application
Attach to the torque arm a set of weights equivalent to the displacer weight completely immersed in the liquid of
Higher Specific Gravity used for calibration [HSG CALIB] using the following formula:
d3. Enter and validate the [SPAN]: the [LEVEL:%] value indicated on the display must equal 100.0%. If not, restart the
procedure until very close to this value. See Appendix B.
e. Press the * button when [SAVE] is displayed to validate the [ZERO] and [SPAN] settings.
Displacer Apparent Weight for REF H =
Displacer Actual Weight - (Displacer Actual Volume X [SG CALIB])
i.e. 1362 907 x 1 = 455 g for a standard displacer and water
Displacer Apparent Weight for REF H =
Displacer Actual Weight - (Displacer Actual Volume X [HSG CALIB])