68 | GE Oil & Gas ® 2014 General Electric Company. All rights reserved.
APPENDIX C
SCREEN DESCRIPTION FOR ADVANCED SETUP MENU 2/2
SMART FILTERING
Validate by pressing the * to enter the Smart Filtering menu.
SMART FILTERING ON
Activate the Smart Filtering function.
SMART FILTERING OFF
Deactivate the Smart Filtering function.
TUNE
Validate by pressing the * to manually or automatically tune the smart filtering
parameters.
DEAD ZONE of
INTEGRATION : %
Manual adjustment of this parameter between 0.01% and 10%.
WINDOW of VALIDATION: s
Manual adjustment of this parameter between 0.1 s and 32 s.
AUTOMATIC TUNE
Validate by pressing the * to automatically tune the smart filtering parameters.
BACK
Return to previous menu.
SPECIFIC GRAVITY METER
CALIBRATION
Validate by pressing the * to calibrate the Specific Gravity Meter. Enter the sub-menu
and proceed as a normal level calibration.
SPECIFIC GRAVITY for
CALIBRATION
Validate by pressing the * to set the specific gravity of the liquid used during the
calibration procedure. Settable value ranges from 0.001 to 10.
ZERO
When displayed, empty the tank (or simulate) so that displacer is fully out of liquid. Wait
till the displacer is stable then press * to define the zero, which is the Reference Low (REF
L).
SPAN
When displayed, fill the tank (or simulate) so that displacer is fully immersed in liquid.
Wait till the displacer is stable then press * to define the span, which is the Reference
High (REF H).
CANCEL
Validate by pressing the * to cancel the parameters saving procedure.
SAVE
Validate by pressing the * to start the saving procedure of parameters previously
entered in the instrument memory.