® 2014 General Electric Company. All rights reserved. Masoneilan 12400 Series Transmitter/Controller Instruction Manual | 75
APPENDIX F
SCREEN DESCRIPTION FOR VIEW DATA MENU
* DLT REVISION
Indicates current instrument revision (firmware and hardware).
* SIL 2 / NON SIL
Indicates if the device is configured as a SIL 2 certified instrument or not.
* BASIC SETUP
Validate by pressing the * to read current Basic Setup data.
* ADVANCED SETUP
Validate by pressing the * to read current Advanced Setup data.
* DIAGNOSTIC
Validate by pressing the * to enter the Diagnostic menu.
READ COUNTER
Validate by pressing the * to enter the sub-menu of cumulated Diagnostic data.
NUMBER of FILLINGS
Totalizes the amount of liquid entering the tank. Counter increments by one when
accumulated positive change in level corresponds to one height of displacer.
TIME LOW
Time (number of hours) during which the instrument worked within +/-5
calibrated value.
TIME HIGH
Time (number of hours) during which the instrument worked within +/-5 %
that is between 95 % and 105 % of calibrated value.
TIME WORKING
Time (number of hours) during which the instrument has been on service.
↑ BACK
Return to previous menu.
RESET COUNTER
Validate by pressing the * to reset the diagnostic data to zero in memory.
SENSOR TEMPERATURE
Indicates sensor circuit board temperature.
MODULE
TEMPERATURE
Indicates main circuit board temperature.
↑ BACK
Return to previous menu.
* SPECIFIC GRAVITY
METER
Validate by pressing the * to read the Specific Gr
avity value of the liquid when the
displacer is fully immersed. The Specific Gravity Meter must have been previously
calibrated. If the Specific Gravity Meter has not been calibrated, the screen ERROR is
displayed: this is the only way to know if the Specific Gravity Meter has been previously
calibrated. In both cases, push * to return to main Diagnostic menu.
ERROR
Displayed when the Specific Gravity Meter has not been calibrated.
↑ BACK
Return to previous menu.