Actual Values, Pg. 7 3 SETUP AND USE
Page Line Information Line Description
3-15
7 1
PAGE 7: ACTUAL VALUESPAGE 7: ACTUAL VALUES
METERING DATAMETERING DATA
ACTUAL VALUES page 7 header
2
METER MODULEMETER MODULE
NOT INSTALLEDNOT INSTALLED
Appears if meter not on-line (setpoints page 7
line 2)
3
PHASE TO PHASEPHASE TO PHASE
VOLTAGE CONNECTIONVOLTAGE CONNECTION
Appears whether or not the meter is online.
When the meter is online, this message dis-
plays the VT configuration as connected to the
meter. See Figure 2.15, 2.16a, 2.16b and 2.23
through 2.29.
This message is displayed when the meter’s
VTs are wired to measure for phase to phase
voltage.
3
PHASE TO NEUTRALPHASE TO NEUTRAL
VOLTAGE CONNECTIONVOLTAGE CONNECTION
This message is displayed when the meter’s
VTs are wired for phase to neutral voltage
measurement.
4
Vab = XXXX Vbc = XXXXVab = XXXX Vbc = XXXX
Vca = XXXX AVG.= XXXX VVca = XXXX AVG.= XXXX V
Appears whether or not the meter is online.
3 phase to phase voltages. Displayed when the
VT configuration above is phase to phase.
4
Van = XXXX Vbn = XXXXVan = XXXX Vbn = XXXX
Vcn = XXXX AVG.= XXXX VVcn = XXXX AVG.= XXXX V
3 phase to neutral voltages. Displayed only
when the VT configuration is phase to neutral.
5
3 PHASE KWATTS3 PHASE KWATTS
KW = +XXXXXKW = +XXXXX
Positive or negative 3 phase kwatts.
See Figure 3.7 for power measurement con-
ventions.
6
3 PHASE KVARS3 PHASE KVARS
KVAR = +XXXXXKVAR = +XXXXX
Positive or negative 3 phase kvars.
See Figure 3.7 for power measurement con-
ventions.
7
POWER FACTORPOWER FACTOR
PF = X.XX LAGPF = X.XX LAG
Power factor and Lead or Lag sign..
See Figure 3.7 for power measurement con-
ventions.
8
FREQUENCYFREQUENCY
HZ = XX.XHZ = XX.X
Frequency
9
END OF PAGE SEVENEND OF PAGE SEVEN
ACTUAL VALUESACTUAL VALUES
Last line of page 7
Available only if a GE Multilin MPM meter is installed and on-line (see pg. 7 setpoints, line 2)
To place the relay in ACTUAL VALUES mode, the
ACTUAL VALUES key must be pressed. When this is
done the following flash message will appear for 2 sec-
onds,
ACTUAL VALUES HAS SEVEN ACTUAL VALUES HAS SEVEN
PAGES OF DATA PAGES OF DATA
The display will then show,
PAGE 1: ACTUAL VALUESPAGE 1: ACTUAL VALUES
PHASE CURRENT DATAPHASE CURRENT DATA
which is the beginning of page 1.
If the relay is in SETPOINTS mode or ACTUAL
VALUES mode and no key is pressed for more than
four minutes the display will change to, (factory default
settings)
I1= XXX I2= XXXI1= XXX I2= XXX
I3= XXX (AMPS)I3= XXX (AMPS)
which is the second line in page 1 of ACTUAL VALUES
mode. This default display line can be changed in
page 5 of SETPOINTS mode.
When in this mode the PAGE UP, PAGE DOWN, LINE
UP, and LINE DOWN keys (see section 3.1) can be

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the GE MULTILIN 269 MOTOR MANAGEMENT RELAY Series and is the answer not in the manual?

GE MULTILIN 269 MOTOR MANAGEMENT RELAY Series Specifications

General IconGeneral
BrandGE
ModelMULTILIN 269 MOTOR MANAGEMENT RELAY Series
CategoryRelays
LanguageEnglish

Related product manuals