Setpoints, Pg. 4 3 SETUP AND USE
3-25
PAGE 4: SETPOINT VALUESPAGE 4: SETPOINT VALUES
RELAY CONFIGURATIONRELAY CONFIGURATION
This page is used to assign trip and alarm functions to specific output relays (ie. TRIP, ALARM, AUX. 1, AUX. 2)
on the 269. Each trip/alarm function is assigned separately to the appropriate relay or to "NO" relay. If an alarm
feature is assigned to no relay, it can still become active (ie. cause the appropriate alarm message to be dis-
played if setpoints are exceeded) but no output relay activation will occur. Possible assignments and factory
values are shown below.
Note: Only one TRIP may occur at any one time. TRIP functions and inhibits must therefore be used to
trip or lockout the motor. Once one TRIP or INHIBIT function is active, no other trip or inhibit may occur.
Assign XXXXXXXXXXXXXXXXAssign XXXXXXXXXXXXXXXX
to XXXXXXXXXXXXXX relayto XXXXXXXXXXXXXX relay
Feature Possible Assignments Factory Value Comments
O/L TRIP TRIP or AUX. 1 or TRIP & AUX.1 TRIP RELAY
U/B TRIP TRIP or AUX. 1 or TRIP & AUX.1 TRIP RELAY
S/C TRIP TRIP or AUX. 1 or TRIP & AUX.1 TRIP RELAY
U/C TRIP TRIP or AUX. 1 or TRIP & AUX.1 TRIP RELAY
RAPID TRIP TRIP or AUX. 1 or TRIP & AUX.1 TRIP RELAY
STATOR RTD TRIP TRIP or AUX. 1 or TRIP & AUX.1 TRIP RELAY
RTD TRIP TRIP or AUX. 1 or TRIP & AUX.1 TRIP RELAY
G/F TRIP TRIP or AUX. 1 or TRIP & AUX.1 TRIP RELAY
ACCEL. TIME TRIP TRIP or AUX. 1 or TRIP & AUX.1 TRIP RELAY
PHASE REVERSAL TRIP TRIP or AUX. 1 or TRIP & AUX.1 TRIP RELAY METER OPTION
INHIBIT LOCKOUTS TRIP or AUX. 1 or TRIP & AUX.1 AUX. 1 RELAY
SINGLE PHASE TRIP or AUX. 1 or TRIP & AUX.1 TRIP RELAY
U/V TRIP TRIP or AUX. 1 or TRIP & AUX.1 TRIP RELAY METER OPTION
O/V TRIP TRIP or AUX. 1 or TRIP & AUX.1 TRIP RELAY METER OPTION
POWER FACTOR TRIP TRIP or AUX. 1 or TRIP & AUX.1 TRIP RELAY METER OPTION
O/L WARNING ALARM or AUX. 1 or AUX. 2 or NO ALARM RELAY
G/F ALARM ALARM or AUX. 1 or AUX. 2 or NO ALARM RELAY
U/B ALARM ALARM or AUX. 1 or AUX. 2 or NO ALARM RELAY
U/C ALARM ALARM or AUX. 1 or AUX. 2 or NO ALARM RELAY
MECH. JAM ALARM ALARM or AUX. 1 or AUX. 2 or NO AUX. 1 RELAY
STATOR RTD ALARM ALARM or AUX. 1 or AUX. 2 or NO ALARM RELAY
RTD ALARM ALARM or AUX. 1 or AUX. 2 or NO AUX. 1 RELAY
NO SENSOR ALARM ALARM or AUX. 1 or AUX. 2 or NO AUX. 1 RELAY
LOW TEMP. ALARM ALARM or AUX. 1 or AUX. 2 or NO AUX. 1 RELAY
T.C. ALARM ALARM or AUX. 1 or AUX. 2 or NO NO RELAY
U/V ALARM ALARM or AUX. 1 or AUX. 2 or NO ALARM RELAY METER OPTION
O/V ALARM ALARM or AUX. 1 or AUX. 2 or NO ALARM RELAY METER OPTION
PF ALARM ALARM or AUX. 1 or AUX. 2 or NO ALARM RELAY METER OPTION
KVAR ALARM ALARM or AUX. 1 or AUX. 2 or NO ALARM RELAY METER OPTION
METER ALARM ALARM or AUX. 1 or AUX. 2 or NO AUX. 2 RELAY
SELF TEST FAIL ALARM or AUX. 1 or AUX. 2 or NO AUX. 2 RELAY
These messages are not displayed when no RTDs are connected to the 269.