3 SETUP AND USE Setpoints, Pg. 5
3-26
1
PAGE 5: SETPOINT VALUESPAGE 5: SETPOINT VALUES
SYSTEM CONFIGURATIONSYSTEM CONFIGURATION
This page is used to configure the 269 relay to exactly match the motor and motor system being pro-
tected. Various special features can be selected, defeated, or adjusted in this page of setpoints.
2
NORMAL RUN DISPLAY SHOWSNORMAL RUN DISPLAY SHOWS
LINE = LINE XXLINE = LINE XX
This setpoint determines the line of the selected page in ACTUAL VALUES MODE to which the display
will return if no key is pressed for more than four minutes and no trips or alarms are present:
1-40 - line number in selected page (see Table 3-2)
Factory Value = 2
3
NORMAL RUN DISPLAY SHOWSNORMAL RUN DISPLAY SHOWS
PAGE = PAGE XXPAGE = PAGE XX
This setpoint determines the page in ACTUAL VALUES mode to which the display will return if no key is
pressed for more than four minutes and no trips or alarms are present:
1 - page 1 (see Table 3-2)
2 - page 2
3 - page 3
4 - page 4
5 - page 5
6 - page 6
Factory Value = 1
4 •
DEFEAT NO SENSOR ALARM?DEFEAT NO SENSOR ALARM?
XXX XXX
This setpoint is used to enable or defeat the Broken RTD Sensor Alarm. This alarm will only become
active for open circuit RTDs chosen for use:
YES - RTD Broken Sensor Alarm defeated.
NO - RTD Broken Sensor Alarm enabled.
Factory Value = YES
5 •
ENABLE LOW TEMPERATUREENABLE LOW TEMPERATURE
ALARM? XXXALARM? XXX
This setpoint is used to enable or defeat the RTD LOW TEMP. ALARM. This alarm will only become ac-
tive for RTD’s measuring 0°C (32°F) (see section 3.16–3.17).
YES - RTD Low Temperature Alarm enabled
NO - RTD Low Temperature Alarm disabled.
Factory Value = NO
• Messages are not displayed if the answer to the question “ARE THERE ANY RTDs CONNECTED” is “NO”.
This setpoint is located on page 2 of setpoints, line 3.