CHAPTER 4: ELECTRICAL INSTALLATION 489 TO 889 SLOT F, H
MULTILIN 489 TO 889 RETROFIT KIT – INSTRUCTION MANUAL 25
Table 4–6: Contact Outputs
Type Function 489 889
Contact Output Trip NO E2 F1
Contact Output Trip Comm F1 F2
Contact Output Trip NC E1 N/A
Contact Output Trip Coil Supervision + E11 Jumper from
F1 to F3
Contact Output Trip Coil Supervision - F11
Contact Output Close Coil Supervision + N/A Jumper from
F4 to F6
Contact Output Close Coil Supervision - N/A
Contact Output Aux 2 NO / Close NO F2 F4
Contact Output Aux 2 Comm / Close Comm E3 F5
Contact Output Aux 2 NC / Close NC F3 N/A
Contact Output Aux 3 NO / Aux 11 NO E5 H9
Contact Output Aux 3 Comm / Aux 11 Comm F4 H8
Contact Output Aux 3 NC / Aux 11 NC E4 H7
Contact Output Aux 4 / Aux 4 NO F5 F12
Contact Output Aux 4 / Aux 4 Comm E6 F11
Contact Output Aux 4 / Aux 4 NC F6 F10
Contact Output Alarm NO E8 F9
Contact Output Alarm Comm F7 F8
Contact Output Alarm NC E7 F7
Contact Output Service NO F8 F24
Contact Output Service Comm E9 F23
Contact Output Service NC F9 F22