26 MULTILIN 489 TO 889 RETROFIT KIT – INSTRUCTION MANUAL
489 TO 889 SLOT F, H CHAPTER 4: ELECTRICAL INSTALLATION
4.4.2 HV I/O - Contact Inputs
NOTE
Note
Setpoint Access and Test Mode is configurable in 889
Set contact input voltage threshold to 17 Vdc for slots F and H
489
889
Table 4–7: HV I/O Contact Inputs
Type Function 489 889
Contact inputs Assignable Input 1 D16 F13 (CI1)
Contact inputs Assignable Input 2 D17 F14 (CI2)
Contact inputs Assignable Input 3 D18 F15 (CI3)
Contact inputs Assignable Input 4 D19 F16 (CI4)
Contact inputs Assignable Input 5 D20 F17 (CI5)
Contact inputs Assignable Input 6 D21 F18 (CI6)
Contact inputs Assignable Input 7 D22 F19 (CI7)
Contact inputs Common D23 F21
Contact inputs Switch +24VDC D24 H21
Contact inputs Set point Access + C1 H13
Contact inputs Set point Access - C2 NA
Contact inputs Breaker Status + C3 H14
Contact inputs Breaker Status - C4 NA