CHAPTER 6: SPECIFICATIONS
G500 SUBSTATION GATEWAY INSTRUCTION MANUAL GE INFORMATION 75
These tests were conducted with all interfaces loaded at typical load conditions.
Altitude
Maximum operating altitude is 2000m.
Above this altitude the isolation requirements for substations (IEC61010-1) couldn’t be
guaranteed. Thermal de-rating due to altitude is characterized in the table below:
Ingress Protection (IEC 60529)
IP30 (protected from tools and wires greater than 2.5 millimeters).
Liquid Protection
The G500 is designed to protect the internal electronics from small amounts of liquid
falling vertically or which may accumulate on the top surface of the chassis.
Mean Time Between Failure
G500 System 2 Core 8GB, 8 serial ports without PSU has slightly higher MTBF.
Altitude Temperature de-rating
2500m 5°C
3000m 10°C
Part GE Part
Number
Failure In
Time (FIT)
MTBF in hours
@40°C
MCP Core System
G500 System 4 Core* 16GB, 8 Serial ports,
w/o PSU
528-0002LF*
(528-0001LF)
15779.6 63373
Power Supplies
HV PSU 528-2001LF 3830.5 261062
LV PSU 528-2002LF 3567.0 280347
PCIe add in cards
4 port Serial PCIe card 528-1001LF 2911.2 343498
SFP Modules, Max 6 combined types
SFP Module 100/1000BASE-T RJ45 TRANS-
CEIVER COPPER
580-3786 134.8 7417297
SFP Module 100BASE-FX LC TRANSCEIVER
OPTICAL
580-3784 228.2 4382121
SFP Module 1000BASE-SX LC TRANS-
CEIVER OPTICAL