GEK-113000T F650 Digital Bay Controller 5-1
5 BOOTCODE AND FIRMWARE UPGRADE 5.1 INTRODUCTION
5
5 BOOTCODE AND FIRMWARE UPGRADE 5.1INTRODUCTION
This section explains how to upgrade the F650 boot code and firmware.
The boot code and firmware versions can be seen in the relay main screen: The relay firmware version appears after the
text "F650" (1.20 in the example) with the boot program version (2.20 in the example) followed by “GENERAL ELECTRIC”,
the relay model and the default front RS232 port communication parameters.
Figure 5–1: MAIN SCREEN
BOOT CODE RELEASE NOTES
It is mandatory to maintain version compatibility between firmware and boot code in the upgrade procedure, otherwise the
relay will not start after upgrading.
WARNING
BEFORE PERFORMING THE UPGRADE PROCEDURE CHECK THAT BOOT AND FIRMWARE VERSION MATCH
FIRMWARE AND BOOT VERSIONS COMPATIBILITY
FIRMWARE VERSION BOOT VERSION
3.70 4.00-4.10
3.60 4.00-4.10
3.44 4.00-4.10
3.40 4.00-4.10
3.20 4.00-4.10
3.00 4.00-4.10
2.20 4.00-4.10
1.82 4.00-4.10
2.0 3.00
1.8X 2.35
1.7X 2.35
1.6X 2.35
1.5X 2.30
1.4X 2.30
1.3X 2.30
1.2X 2.20
1.13 2.20
1.11 2.00
1.00 2.00